H8PS  
Safety Precautions for Cam Positioners  
Refer to Safety Precautions for All Counters.  
Precautions for Safe Use  
!CAUTION  
Observe the following items to ensure the safe use of this product.  
Tighten terminal screws to a torque of 0.80 N·m so that  
they do not become loose.  
Minor fires or malfunction may occasionally occur.  
Environmental Precautions  
Store the H8PS within specified ratings. If the H8PS has been  
stored at temperatures 10°C or lower, let it stand for 3 hours or  
longer at room temperature before turning ON the power supply.  
Use the H8PS within the specified ratings for operating temperature  
and humidity.  
Do not operate the H8PS in locations subject to sudden or extreme  
changes in temperature, or locations where high humidity may  
result in condensation.  
For 16- and 32-output Models, leave the protective label  
attached to the H8PS when wiring. Removing the label  
before wiring may occasionally result in fire if foreign  
matter enters the Unit.  
Remove the label after the completion of wiring to ensure  
proper heat dissipation. Leaving the label attached may  
occasionally result in fire.  
Do not disassemble, modify, or repair the H8PS or touch  
any of the internal parts. Otherwise, minor electric shock,  
fire, or malfunction may occasionally occur.  
Do not use the H8PS in locations subject to vibrations or shock.  
Extended use in such locations may result in damage due to stress.  
Do not use the H8PS in locations subject to excessive dust,  
corrosive gas, or direct sunlight.  
Install the H8PS well away from any sources of static electricity,  
such as pipes transporting molding materials, powders, or liquids.  
The H8PS is not waterproof or oil resistant.  
Do not use it in locations subject to water or oil.  
The life expectancy of internal components may be reduced if the  
H8PS is mounted side-by-side.  
Do no allow metal fragments, lead wire scraps, or chips  
from processing during installation to fall inside the H8PS.  
Otherwise, minor electric shock, fire, or malfunction may  
occasionally occur.  
Do not touch the terminals when power is being supplied.  
For Surface-mounting H8PS, always connect the terminal  
cover for after completing wiring. Otherwise, minor injury  
due to electric shock may occasionally occur.  
Do not use organic solvents (such as paint thinner or benzine),  
strong alkaline, or strong acids because they will damage the  
external finish.  
Usage Precautions  
Install a switch or circuit breaker that allows the operator to  
immediately turn OFF the power, and label it to clearly indicate its  
function.  
Pay careful attention to polarity to avoid wrong connections when  
wiring terminals.  
Do not connect more than two crimp terminals to the same  
terminal.  
Use the specified wires for wiring.  
Applicable Wires  
AWG24 to AWG18 (cross-sectional area of 0.208 to 0.832 mm2)  
Solid or twisted wires of copper  
Do not connect loads that exceed the rated output current. The  
output elements may be destroyed, possibly resulting in short-  
circuit or open-circuit faults.  
Always connect a diode to protect against counterelectromotive  
force when using an inductive load. Counterelectromotive force  
may destroy output elements, possibly resulting in short-circuit or  
open-circuit faults.  
Use the specified cables to connect outputs.  
Do not install input lines in the same duct or conduit as power  
supply or other high-voltage lines. Doing so may result in  
malfunction due to noise. Separate the input lines from high-  
voltage lines.  
Internal elements may be destroyed if a voltage outside the rated  
voltage is applied.  
Maintain voltage fluctuations in the power supply within the  
specified range.  
Use a switch, relay, or other contact so that the rated power supply  
voltage will be reached within 0.1 s. If the power supply voltage is  
not reached quickly enough, the H8PS may malfunction or outputs  
may be unstable.  
Do not turn OFF the power supply when changing or deleting  
settings. The contents of the EEPROM may be corrupted.  