I/O Expansion Adapters
Use Expansion I/O adapters to split the configuration into more
than one group, allowing greater flexibility with mounting space
as well as the use of at least 16 I/O Modules or Dedicated I/O
Modules. Expansion Adapters can be used with any CQM1H
CPU.
CQM1H-IC101
CQM1H-II101
J SPECIFICATIONS
Maximum Number of Units Mountable
CPU Block only
CPU grouping
CPU Block + I/O Expansion Adapter
CPU grouping
CPU model
Extension grouping
I/O Modules + Dedi-
cated I/O Modules
Controller Link
Modules
Inner Boards
I/O Modules + Dedi-
cated I/O Modules
I/O Modules + Dedi-
cated I/O Modules
11 Modules max.
1 Module
2 Boards max.
5 Modules max.
11 Modules max.
CQM1H-CPU61
CQM1H-CPU51
CQM1H-CPU21
CQM1H-CPU11
Not supported
Not supported
J CONFIGURATION
5 Modules max.
CPU Grouping
I/O Control Adapter
(CQM1H-IC101)
Total current consumption:
3.0 A max. (including CPU)
End Cover
(included with CPU Unit)
I/O Extension Cable
CS1W-CN313 (0.3 m) or
CS1W-CN713 (0.7 m)
Extension Grouping
Total current consumption:
2.0 A max. (I/O Modules and
Dedicated I/O Modules)
End Cover
(included with I/O
Interface Module)
I/O Interface Adapter
(CQM1H-II101)
11 Modules max.
Note: If the CQM1-PA203 Power
Supply Unit is used, the
maximum current con-
sumption total is 3.6 A.
A--165
Programmable Controller CQM1H