CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@  
General Specifications  
Type  
AC power supply models  
DC power supply models  
Model  
CP1E-@@@D@-A  
CP1E-@@@D@-D  
Enclosure  
Mounted in a panel  
CPU Unit with 10 I/O points (CP1E-E10D@-@): 90mm *1 ×85mm *2 × 66 mm  
CPU Unit with 14 or 20 I/O points (CP1E-@14D@-@/@20D@-@): 90mm *1 × 85mm *2 × 86 mm  
CPU Unit with 30 I/O points (CP1E-@30D@-@): 90mm *1 × 85mm *2 × 130 mm  
CPU Unit with 40 I/O points (CP1E-@40D@-@): 90mm *1 × 85mm *2 × 150 mm  
CPU Unit with 60 I/O points (CP1E-N60D@-@): 90mm *1 ×85mm *2 × 195 mm  
CPU Unit with 20 I/O points and built-in analog (CP1E-NA20D@-@): 90mm *1 ×85mm *2 × 130 mm  
Dimensions (H × D × W)  
CPU Unit with 10 I/O points (CP1E-E10D@-@): 300g max.  
CPU Unit with 14 I/O points (CP1E-@14D@-@): 360g max.  
CPU Unit with 20 I/O points (CP1E-@20D@-@): 370g max.  
CPU Unit with 30 I/O points (CP1E-@30D@-@): 600g max.  
CPU Unit with 40 I/O points (CP1E-@40D@-@): 660g max.  
CPU Unit with 60 I/O points (CP1E-N60D@-@): 850g max.  
CPU Unit with 20 I/O points and built-in analog (CP1E-NA20D@-@): 680g max.  
Weight  
Supply voltage  
100 to 240 VAC 50/60 Hz  
24 VDC  
Operating voltage  
range  
85 to 264 VAC  
20.4 to 26.4 VDC  
15 VA/100 VAC max.  
25 VA/240 VAC max.  
(CP1E-E10D@-A/@14D@-A/@20D@-A)  
9 W max. (CP1E-E10D@-D)  
13 W max. (CP1E-N14D@-D/N20D@-D)  
Power consumption  
Inrush current  
50 VA/100 VAC max.  
70 VA/240 VAC max.  
(CP1E-NA20D@-A/@30D@-A/@40D@-A/N60D@-A)  
20 W max.  
(CP1E-NA20D@-D/N30D@-D/N40D@-D/N60D@-D) *4  
120 VAC, 20 A for 8 ms max. for cold start at room  
temperature  
240 VAC, 40 A for 8 ms max. for cold start at room  
temperature  
24 VDC, 30 A for 20 ms max. for cold start at room  
temperature  
Electrical  
specifications  
Not provided.  
External power supply  
*3  
(CP1E-E10D@-A/@14D@-A/@20D@-A)  
Not provided  
24 VDC, 300 mA  
(CP1E-NA20D@-A/@30D@-A/@40D@-A/N60D@-A)  
20 MΩ min. (at 500 VDC) between the external AC  
Except between DC primary current and DC  
secondary current  
Insulation resistance  
Dielectric strength  
terminals and GR terminals  
2,300 VAC 50/60Hz for 1 min between AC external  
and GR terminals Leakage current: 5 mA max.  
Except between DC primary current and DC  
secondary current  
Power OFF detection  
time  
10 ms min.  
0 to 55 °C  
2 ms min.  
Ambient operating  
temperature  
Ambient humidity  
Atmosphere  
10% to 90%  
No corrosive gas.  
Ambient storage  
temperature  
-20 to 75 °C (excluding battery)  
Altitude  
2,000 m max.  
Application  
environment  
Pollution degree  
Noise resistance  
Overvoltage category  
EMC Immunity Level  
2 or less: Conforms to JIS B3502 and IEC 61131-2.  
2 kV on power supply line (Conforms to IEC61000-4-4.)  
Category II: Conforms to JIS B3502 and IEC 61131-2.  
Zone B  
Conforms to JIS 60068-2-6.  
Vibration resistance  
Shock resistance  
5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz  
Acceleration of 9.8 m/s2 for 100 min in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total)  
Conforms to JIS 60068-2-27.  
147 m/s2, 3 times in X, Y, and Z directions  
Terminal block  
Fixed (not removable)  
M3  
Terminal screw size  
Applicable standards  
Grounding method  
Conforms to EC Directive  
Ground to 100 Ω or less.  
* 1 Total of 110 mm with mounting brackets.  
* 2 Excluding cables.  
* 3 Use the external power supply to power input devices. Do not use it to drive output devices.  
* 4 This is the rated value for the maximum system configuration. Use the following formula to calculate power consumption for CPU Units with  
DC power.  
Formula: DC power consumption = (5V current consumption 5 V/70% (internal power efficiency) + 24V current consumption) 1.1(current  
fluctuation factor)  
The above calculation results show that a DC power supply with a greater capacity is required.  