CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@
Expansion I/O Units and Expansion Units (for CP1E E30/40, N30/40/60, or NA20 CPU Units)
CP1E E10/14/20 or N14/20 CPU Units do not support Expansion I/O Units and Expansion Units.
Current
consumption (A)
Specifications
Unit type
Product name
Input Unit
Model
Standards
Inputs
Outputs
Output type
5 V
24 V
8
--
--
0.018
--
CP1W-8ED
U, C, N, L, CE
Output Units
Relay
0.026
0.075
0.044
--
CP1W-8ER
CP1W-8ET
Transistor
(sinking)
--
--
8
Transistor
(sourcing)
0.075
0.042
0.076
--
0.090
--
CP1W-8ET1
CP1W-16ER
CP1W-16ET
Relay
Transistor
(sinking)
16
32
8
N, L, CE
Transistor
(sourcing)
0.076
0.049
0.113
--
0.131
--
CP1W-16ET1
CP1W-32ER
CP1W-32ET
CP1W
Expansion I/O
Units
Relay
Transistor
(sinking)
--
N, L, CE
Transistor
(sourcing)
0.113
0.103
0.130
--
0.044
--
CP1W-32ET1
CP1W-20EDR1
CP1W-20EDT
I/O Units
Relay
Transistor
(sinking)
12
U, C, N, L, CE
Transistor
(sourcing)
0.130
0.080
0.160
--
0.090
--
CP1W-20EDT1
CP1W-40EDR
CP1W-40EDT
Relay
Transistor
(sinking)
24
16
N, L, CE
Transistor
(sourcing)
0.160
--
CP1W-40EDT1
Analog Input Unit
4 analog inputs
Input range: 0 to 5 V, 1 to 5 V, 0 to 10 V, 10 V,
0 to 20 mA, or 4 to 20 mA.
0.100
0.090
CP1W-AD041
UC1, N, L, CE
Resolution: 1/6000
2 analog outputs
Output range: 1 to 5 V, 0 to 10 V, 10 V,
0 to 20 mA, or 4 to 20 mA.
Resolution: 1/6000
0.040
0.080
0.095
0.124
UC1, CE
Analog Output Unit
CP1W-DA021
CP1W-DA041
4 analog outputs
Output range: 1 to 5 V, 0 to 10 V, 10 V,
0 to 20 mA, or 4 to 20 mA.
Resolution: 1/6000
UC1, N, L, CE
2 analog inputs and 1 analog output
Input range: 0 to 5 V, 1 to 5 V, 0 to 10 V, 10 V,
0 to 20 mA, or 4 to 20 mA.
Analog I/O Unit
0.083
0.110
CP1W-MAD11
Output range: 1 to 5 V, 0 to 10 V, 10 V,
CP1W
Expansion
Units
0 to 20 mA, or 4 to 20 mA.
Resolution: 1/6000
Temperature
Sensor Unit
2 temperature sensor inputs
Sensor type: Thermocouple (J or K)
0.040
0.040
0.059
0.059
CP1W-TS001
CP1W-TS002
4 temperature sensor inputs
Sensor type: Thermocouple (J or K)
2 temperature sensor inputs
Sensor type: Platinum resistance thermometer
(Pt100 or JPt100)
U, C, N, L, CE
0.054
0.054
0.073
0.073
CP1W-TS101
CP1W-TS102
4 temperature sensor inputs
Sensor type: Platinum resistance thermometer
(Pt100 or JPt100)
CompoBus/S
I/O Link Unit
CompoBus/S slave
8 inputs and 8 outputs
0.029
--
CP1W-SRT21
I/O Connecting Cable
Product name
Specifications
Model
CP1W-CN811
Standards
UC1, N, L, CE
80 cm (for CP1W Expansion I/O Units and Expansion Units)
Only one I/O Connecting Cable can be used in each PLC.
I/O Connecting Cable
Note: An I/O Connecting Cable (approx. 6 cm) for horizontal connection is provided with CP1W Expansion I/O Units and Expansion Units.
7