欢迎访问ic37.com |
会员登录 免费注册
发布采购

TDA8589AJ 参数 Datasheet PDF下载

TDA8589AJ图片预览
型号: TDA8589AJ
PDF下载: 下载PDF文件 查看货源
内容描述: I2C总线控制4 45瓦功率放大器和多电压调节器 [I2C-bus controlled 4 45 Watt power amplifier and multiple voltage regulator]
分类和应用: 调节器消费电路商用集成电路放大器功率放大器局域网
文件页数/大小: 55 页 / 540 K
品牌: NXP [ NXP ]
 浏览型号TDA8589AJ的Datasheet PDF文件第5页浏览型号TDA8589AJ的Datasheet PDF文件第6页浏览型号TDA8589AJ的Datasheet PDF文件第7页浏览型号TDA8589AJ的Datasheet PDF文件第8页浏览型号TDA8589AJ的Datasheet PDF文件第10页浏览型号TDA8589AJ的Datasheet PDF文件第11页浏览型号TDA8589AJ的Datasheet PDF文件第12页浏览型号TDA8589AJ的Datasheet PDF文件第13页  
Philips Semiconductors  
Product specication  
I2C-bus controlled 4 45 Watt power  
amplier and multiple voltage regulator  
TDA8589J; TDA8589xJ  
compared with a reference voltage. If the output voltage of  
a channel is greater than the reference voltage, bit D2 of  
the associated data byte is set and read by the  
microcontroller during a read instruction. Note that the  
value of this bit is only meaningful when there is no input  
signal and the amplifier is not muted. Offset detection is  
always enabled.  
AC-LOAD DETECTION  
AC-load detection can be used to detect that AC-coupled  
speakers are connected correctly during assembly. This  
requires at least 3 periods of a 19 kHz sine wave to be  
applied to the amplifier inputs. The amplifier produces a  
peak output voltage which also generates a peak output  
current through the AC-coupled speaker. The 19 kHz sine  
wave is also audible during the test. If the amplifier detects  
three current peaks that are greater than 550 mA, the  
AC-load detection bit D1 of instruction byte IB1 is set to  
logic 1. Three current peaks are counted to avoid false  
AC-load detection which can occur if the input signal is  
switched on and off. The peak current counter can be reset  
by setting bit D1 of instruction byte IB1 to logic 0.  
To guarantee AC-load detection, an amplifier current of  
more than 550 mA is required. AC-load detection will  
never occur with a current of less than 150 mA. Figure 3  
shows which AC loads are detected at different output  
voltages. For example, if a load is detected at an output  
voltage of 2.5 V peak, the load is less than 4 . If no load  
Speaker protection  
If one side of a speaker is connected to ground, a missing  
current protection is implemented to prevent damage to  
the speaker. A fault condition is detected in a channel  
when there is a mismatch between the power current in the  
high side and the power current in the low side; during a  
fault condition the channel will be switched off.  
The load status of each channel can be read via the  
I2C-bus: short to ground (one side of the speaker  
connected to ground), short to VP (one side of the speaker  
connected to VP), and shorted load.  
is detected, the output impedance is more than 14  
.
Line driver mode  
An amplifier can be used as a line driver by switching it to  
low gain mode. In normal mode, the gain between  
single-ended input and differential output (across the load)  
is 26 dB. In low gain mode the gain between single-ended  
input and differential output is 20 dB.  
2
10  
(1)  
(2)  
no load present  
Z
o(load)  
(
)
Input and AC ground capacitor values  
The negative inputs to all four amplifier channels are  
combined at pin ACGND. To obtain the best performance  
for supply voltage ripple rejection and unwanted audible  
noise, the value of the capacitor connected to pin ACGND  
must be as close as possible to 4 times the value of the  
input capacitor connected to the positive input of each  
channel.  
undefined  
10  
load present  
Load detection  
1
0
2.5  
5
7.5  
V
10  
(V)  
DC-LOAD DETECTION  
o(peak)  
When DC-load detection is enabled, during the start-up  
cycle, a DC-offset is applied slowly to the amplifier outputs,  
and the output currents are measured. If the output current  
of an amplifier rises above a certain level, it is assumed  
that there is a load of less than 6 and bit D5 is reset in  
the associated data byte register to indicate that a load is  
detected.  
(1) IO(peak) = < 150 mA.  
(2) IO(peak) = > 550 mA.  
Fig.3 Tolerance of AC-load detection as a  
function of output voltage.  
Because the offset is measured during the amplifier  
start-up cycle, detection is inaudible and can be performed  
every time the amplifier is switched on.  
LOAD DETECTION PROCEDURE  
1. At start-up, enable the AC- or DC-load detection by  
setting D1 of instruction byte 1 to logic 1.  
2004 Feb 24  
9
 复制成功!