PDSP16256
Using a Remote Master
When a remote master is used to load
The address and coefficient buses plus
the and signals must all meet the specified
coefficients,
must be tied high and a
EPROM
WEN
CS
conventional peripheral interface is then provided. It
is not possible, however, to read coefficients already
stored. The master supplies an address and data
bus, and writes to the PDSP16256 occur under the
set up and hold times with respect to the system
clock, see Fig 20 and Switching Characteristics.
This synchronous interface is optimum for the
majority of high end applications, when individual
coefficients must be updated at sample clock rates.
However, if the coefficients are to be loaded under
software control from a general purpose
control of synchronous
and
inputs. The
WEN
CS
CoefficientControlRegisterpin(CCS)mustbedriven
by a master address line higher in significance than
A7:0. Both the
and
signals must be low for
CS
WEN
microprocessor, the processor’s
will
WRITE STROBE
the load operation to occur. When loading the control
register the signal must be held low for a further 2
cycles, see Fig. 20. Since the internal write operation
is actually performed with the system clock, it is
necessary for the clock to be present during the
transfer.
probably be asynchronous with the SCLK clock
used by the PDSP16256. In this case external
synchronising logic is needed, as shown in Fig.18.
CS
Fig. 19 shows the recommended loading sequence
andfilteroperationinitiation.Thesimplesttechnique
is to reset the device prior to loading a set of
coefficients.CoefficientsmaybeloadedonceBUSY
The
input defines whether coefficients are
BYTE
loaded as a single 16 bit word or two 8-bit bytes. The
latter saves on connections to the remote master.
Address bits A7:0 are used in byte mode. 16-bit word
mode uses bits A6:0, A7 being redundant. When
writing in byte mode the least significant byte (A0 = 0)
must be written first followed by the most significant
byte (A0 = 1).
returns low or 22 cycles after
is taken high.
RES
When loading a device from a remote master the
control register must be loaded first followed by the
filtercoefficients. Fig. 19showstherequiredloading
sequence, two examples are given one for byte
mode the other for word mode. A gap of at least one
cycle must be left after loading the control register
before loading the first coefficient.
InbytemodetheinternalcomparisonbetweenC15:12
andC11:8ismade,regardlessofthestateof
.
EPROM
ForthisreasonpinsC15:8shouldallbetiedlowwhen
a remote master is used with byte transfers. This
ensures that the internal comparison gives equality
and allows the load operation to occur.
Filter operations are started by presenting the first
data word at the same time as raising signal FEN;
FRUN should always be low.
16