欢迎访问ic37.com |
会员登录 免费注册
发布采购

ADE7761BARS 参数 Datasheet PDF下载

ADE7761BARS图片预览
型号: ADE7761BARS
PDF下载: 下载PDF文件 查看货源
内容描述: 电能计量IC ,带有片上故障和中性丢失检测 [Energy Metering IC with On-Chip Fault and Missing Neutral Detection]
分类和应用: 模拟IC信号电路光电二极管
文件页数/大小: 24 页 / 528 K
品牌: ADI [ ADI ]
 浏览型号ADE7761BARS的Datasheet PDF文件第14页浏览型号ADE7761BARS的Datasheet PDF文件第15页浏览型号ADE7761BARS的Datasheet PDF文件第16页浏览型号ADE7761BARS的Datasheet PDF文件第17页浏览型号ADE7761BARS的Datasheet PDF文件第19页浏览型号ADE7761BARS的Datasheet PDF文件第20页浏览型号ADE7761BARS的Datasheet PDF文件第21页浏览型号ADE7761BARS的Datasheet PDF文件第22页  
ADE7761B  
Fault with Active Input Greater Than Inactive Input  
Calibration Concerns  
If V1A is the active current input (that is, being used for billing),  
and the voltage signal on V1B (inactive input) falls below 93.75%  
of V1A, the fault indicator becomes active. Both analog inputs  
are filtered and averaged to prevent false triggering of this logic  
output. As a consequence of the filtering, there is a time delay of  
approximately 3 sec on the Logic Output FAULT after the fault  
event. The FAULT logic output is independent of any activity on  
the F1 or F2 outputs. Figure 28 shows one condition under  
which FAULT becomes active. Because V1A is the active input  
and it is still greater than V1B, billing is maintained on V1A; that  
is, no swap to the V1B input occurs. V1A remains the active input.  
Typically, when a meter is being calibrated, the voltage and current  
circuits are separated, as shown in Figure 30. This means that  
current passes through only the phase or neutral circuit. Figure 30  
shows current being passed through the phase circuit. This is  
the preferred option because the ADE7761B starts billing on the  
input V1A on power-up. The Phase Circuit CT is connected to  
V1A in Figure 30. Because there is no current in the neutral circuit,  
the FAULT indicator comes on under these conditions. However,  
this does not affect the accuracy of the calibration and can be  
used as a means to test the functionality of the fault detection.  
V
R
1A  
F
IB  
CT  
FAULT  
FILTER  
V
V
1A  
1A  
AND  
RB  
RB  
V
COMPARE  
C
A
1B  
V
F
F
1A  
V
V
TO  
1A  
1B  
AGND  
MULTIPLIER  
0V  
V
V
1N  
V
V
1N  
1B  
IB  
0V  
AGND  
C
B
TEST  
CURRENT  
V
< 93.75% OF V  
1A  
1B  
CT  
R
F
1B  
1
RA  
FAULT  
<0  
C
F
1
1
RB  
V
V
2P  
>0  
VR  
ACTIVE POINT – INACTIVE INPUT  
R
F
2N  
6.25% OF ACTIVE INPUT  
V
C
T
Figure 28. Fault Conditions for Active Input Greater Than Inactive Input  
240V rms  
1
RB + VR = RF.  
Fault with Inactive Input Greater Than Active Input  
Figure 30. Conditions for Calibration of Channel B  
Figure 29 illustrates another fault condition. If the difference  
between V1B, the inactive input, and V1A, the active input (that  
is, being used for billing), becomes greater than 6.25% of V1B,  
the FAULT indicator becomes active and a swap over to the V1B  
input occurs. The Analog Input V1B becomes the active input.  
Again, a time constant of about 3 sec is associated with this swap.  
V1A does not swap back to the active channel until V1A is greater  
than V1B, and the difference between V1A and V1B, in this order,  
becomes greater than 6.25% of V1A. However, the FAULT indi-  
cator becomes inactive as soon as V1A is within 6.25% of V1B. This  
threshold eliminates potential chatter between V1A and V1B.  
If the neutral circuit is chosen for the current circuit in the  
arrangement shown in Figure 30, this may have implications for  
the calibration accuracy. The ADE7761B powers up with the  
V1A input active as normal. However, because there is no current  
in the phase circuit, the signal on V1A is zero. This causes a fault  
to be flagged and the active input to be swapped to V1B (neutral).  
The meter can be calibrated in this mode, but the phase and  
neutral CTs may differ slightly. Because under no-fault conditions  
all billing is carried out using the phase CT, the meter should be  
calibrated using the phase circuit. Of course, both phase and  
neutral circuits can be calibrated.  
FAULT  
FILTER  
AND  
V
V
1A  
1A  
MISSING NEUTRAL MODE  
A
V
COMPARE  
1B  
V
V
TO  
1A  
1B  
The ADE7761B integrates a novel fault detection scheme that  
warns and allows the ADE7761B to continue to bill in case a  
meter is connected to only one wire (see Figure 31). For correct  
operation of the ADE7761B in this mode, the VDD pin of the  
ADE7761B must be maintained within the specified range  
(5 V 5%). The missing neutral detection algorithm is designed  
to work over a line frequency of 45 Hz to 55 Hz.  
MULTIPLIER  
0V  
V
V
1N  
1B  
AGND  
B
V
< 93.75% OF V  
1B  
1A  
FAULT + SWAP  
<0  
>0  
ACTIVE POINT – INACTIVE INPUT  
6.25% OF INACTIVE INPUT  
Figure 29. Fault Conditions for Inactive Input Greater Than Active Input  
Rev. 0 | Page 18 of 24