 浏览型号601/003/230/F/00/UK的Datasheet PDF文件第13页浏览型号601/003/230/F/00/UK的Datasheet PDF文件第14页浏览型号601/003/230/F/00/UK的Datasheet PDF文件第15页浏览型号601/003/230/F/00/UK的Datasheet PDF文件第16页浏览型号601/003/230/F/00/UK的Datasheet PDF文件第18页浏览型号601/003/230/F/00/UK的Datasheet PDF文件第19页浏览型号601/003/230/F/00/UK的Datasheet PDF文件第20页浏览型号601/003/230/F/00/UK的Datasheet PDF文件第21页  
(OHFWULFDO#,QVWDOODWLRQ##7#0#6  
by using two independent protective earth incoming supply conductors (figure 4.3).  
This is due to the high earth leakage current when using filters.  
The incoming mains supply should be protected by a suitable fuse or circuit breaker,  
as shown in table 2.1.  
Current Rating  
Cable size  
Cable size  
Power cables should be  
specified to this table:-  
< = 8 Amps  
< = 10 Amps  
< = 15 Amps  
1 mm2  
16 AWG  
14 AWG  
12 AWG  
1.5 mm2  
2.5 mm2  
7DEOH#714  
When the wires are fully inserted into the terminal to maintain IP20 protection they  
need to be stripped to 5 - 6 mm (0.22 in).  
&RQWURO#:LULQJ  
All control and signal terminals are SELV, i.e., protected by double/reinforced  
insulation. Ensure all wiring rated for highest system voltage. Control wiring of  
between 0.08 mm2 (28 AWG) - 2.5 mm2 (14 AWG) can be used.  
Remove the terminal cover (see figure 1.1). Rotate the Control Cable Retainer, route  
the control cables in the right hand compartment and wire to the control terminals.  
Rotate the Control Cable Retainer to hold the cables in the designated compartment.  
Figure 4.4 shows a typical control connections required for operation as a simple  
speed controller.  
43  
4
5
6
7
8
9
:
;
<
* It is recommended that the  
“0V/common” be connected to  
protective earth/ground for safety  
reasons. In a system comprising  
of more than one controller, the  
“0V/common” signals should be  
connected together and joined to  
protective earth/ground at one  
point only. This is mandatory to  
meet the EMC specification  
stated.  
-
+HDOWK#5HOD\  
579#83P$#PD[1  
6SHHG  
6HWSRLQW  
-RJ  
5XQ  
43N  
'LUHFWLRQ  
)LJXUH#717  
934#0##+$79784;#  
(1*/,6+  