欢迎访问ic37.com |
会员登录 免费注册
发布采购

B1101UC4 参数 Datasheet PDF下载

B1101UC4图片预览
型号: B1101UC4
PDF下载: 下载PDF文件 查看货源
内容描述: [Surge Protection Circuit, PDSO6, MODIFIED, MS-013, 6 PIN]
分类和应用: 电信光电二极管电信集成电路
文件页数/大小: 212 页 / 1843 K
品牌: TECCOR [ TECCOR ELECTRONICS ]
 浏览型号B1101UC4的Datasheet PDF文件第125页浏览型号B1101UC4的Datasheet PDF文件第126页浏览型号B1101UC4的Datasheet PDF文件第127页浏览型号B1101UC4的Datasheet PDF文件第128页浏览型号B1101UC4的Datasheet PDF文件第130页浏览型号B1101UC4的Datasheet PDF文件第131页浏览型号B1101UC4的Datasheet PDF文件第132页浏览型号B1101UC4的Datasheet PDF文件第133页  
GR 1089–Core  
AC Power Fault Test is that the EUT may be damaged, but it may not become a fire,  
fragmentation, or electrical safety hazard. Passing criteria for the Current Limiter Test is that  
the EUT may be damaged but it may not exceed the acceptable time/current criteria (that is,  
cannot cause the wiring simulator as shown in Figure 4.2 to open) nor become a fire,  
fragmentation, or electrical safety hazard.  
The indicator used in measuring fire, fragmentation, and electrical safety hazards is a  
bleached, untreated cotton cheesecloth wrapped around the EUT. Compliance with testing  
is determined by the absence of ignition, charring, and the ejection of molten material or  
fragments.  
First Level Lightning Surge Test  
To pass the First Level Lightning Surge Test, the EUT must be undamaged and continue to  
operate properly after the stress is applied. This is referred to as passing “operationally.”  
Table 4.3 presents the conditions for the First Level inter-building criteria. Applicants have  
the option to submit their equipment to meet surges 1, 2, 4, and 5 or surges 3, 4, and 5.  
Table 4.4 presents the conditions for the intra-building criteria.  
Table 4.3 First Level Lightning Surge Test  
Surge Current  
per Conductor  
(A)  
Test  
Test  
Surge Voltage  
(VPK  
Waveform  
(µs)  
Repetitions  
Connections  
(Notes 1 & 2)  
)
Each Polarity  
(Table 4.1, Figure 4.1)  
1
±600  
±1000  
±1000  
±2500  
±1000  
10x1000  
10x360  
10x1000  
2x10  
100  
100  
100  
500  
25  
25  
25  
25  
10  
5
A
A
A
B
B
2 (Note 3)  
3 (Note 3)  
4 (Note 4)  
5 (Note 5)  
10x360  
Notes:  
1. Primary protectors are removed for all tests.  
2. For EUT containing secondary voltage limiting and current limiting protectors, tests are to be performed at the indicated voltage(s)  
and repeated at a reduced voltage and current just below the operating threshold of the secondary protectors.  
3. Test 1 and 2 can be replaced with Test 3 or vice versa.  
4. Alternatively, a surge generator of 1.2x50 µs open-circuit voltage waveform (8x20 µs short-circuit current waveform) per  
IEEE C62.41 may be used. The current shall be limited by the inclusion of a series 3 resistor placed externally to the surge  
generator.  
5. This test is to be performed on up to 12 Tip and Ring pairs simultaneously.  
Table 4.4 Intra-Building Lightning Surge Test  
Surge Current  
Surge Voltage  
Wave-form  
per Conductor  
Repetitions Each  
Polarity  
Test Connections  
Test  
(VPK  
)
(µs)  
(A)  
(Table 4.1, Figure 4.1)  
1
2
±800  
±1500  
2x10  
2x10  
100  
100  
1
1
A1, A2  
B
Notes:  
For EUT containing secondary voltage limiting and current limiting protectors, tests are to be performed at the indicated voltage(s)  
and repeated at a reduced voltage and current just below the operating threshold of the secondary protectors.  
Alternatively, a surge generator of 1.2x50 µs open-circuit voltage waveform (8x20 µs short-circuit current waveform) per  
IEEE C62.41 may be used. The current shall be limited by the inclusion of a series 6 resistor for Test 1 and a 12 resistor for  
Test 2, placed externally to the surge generator.  
© 2002 Teccor Electronics  
4 - 5  
http://www.teccor.com  
+1 972-580-7777  
®
SIDACtor Data Book and Design Guide  
 复制成功!