QS20.241, QS20.241-A1, QS20.241-C1
Q-Series
24V, 20A, SINGLE PHASE INPUT
22.13.MOUNTING ORIENTATIONS
Mounting orientations other than input terminals on the bottom and output on the top require a reduction in
continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction
influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous
operation can be found below:
Curve A1
Curve A2
Recommended output current.
Max allowed output current (results in approximately half the lifetime expectancy of A1).
Fig. 22-6
Output Current
Mounting
Orientation A
(Standard
OUTPUT
20A
16
12
8
A1
orientation)
Power
Supply
4
0
Ambient Temperature
INPUT
10
20
30
40
50
60°C
60°C
60°C
60°C
60°C
Fig. 22-7
Mounting
Output Current
T
P U I N
20A
16
12
8
Orientation B
(Upside down)
A2
A1
S u p p l y
P o w e r
4
0
O U T P U T
Ambient Temperature
20 30 40 50
10
Fig. 22-8
Output Current
Mounting
Orientation C
(Table-top
mounting)
20A
16
12
8
A2
A1
4
0
Ambient Temperature
20 30 40 50
10
Fig. 22-9
Mounting
Orientation D
(Horizontal cw)
Output Current
20A
16
12
8
A2
A1
4
0
Ambient Temperature
20 30 40 50
10
Fig. 22-10
Mounting
Orientation E
(Horizontal ccw)
Output Current
20A
16
12
8
A2
A1
4
0
Ambient Temperature
20 30 40 50
10
Oct. 2013 / Rev. 2.2 DS-QS20.241-EN
All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.