QS20.241, QS20.241-A1, QS20.241-C1  
Q-Series  
24V, 20A, SINGLE PHASE INPUT  
Unit A  
22.9. SERIES OPERATION  
AC  
+
-
Power supplies of the same type can be connected in series for higher  
output voltages. It is possible to connect as many units in series as needed,  
providing the sum of the output voltage does not exceed 150Vdc. Voltages  
with a potential above 60Vdc are not SELV any more and can be dangerous.  
Such voltages must be installed with a protection against touching.  
DC  
+
Load  
Unit B  
AC  
+
-
-
Earthing of the output is required when the sum of the output voltage is  
above 60Vdc.  
Earth  
(see notes)  
DC  
Avoid return voltage (e.g. from a decelerating motor or battery) which is  
applied to the output terminals.  
Keep an installation clearance of 15mm (left / right) between two power supplies and avoid installing the power  
supplies on top of each other. Do not use power supplies in series in mounting orientations other than the standard  
mounting orientation (input terminals on bottom and output terminals on the top of the unit).  
Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple power supplies.  
22.10.INDUCTIVE AND CAPACITIVE LOADS  
The unit is designed to supply any kind of loads, including unlimited capacitive and inductive loads.  
22.11.OPERATION ON TWO PHASES  
Power Supply  
The power supply can also be used on two-phases of a three-phase-system.  
Such a phase-to-phase connection is allowed as long as the supplying  
voltage is below 240V+15%. Use a fuse or a circuit breaker to protect the N  
input. The N input is internally not protected and is in this case connected to  
a hot wire. Appropriate fuses or circuit breakers are specified in section 22.4  
“External Input Protection”.  
L1  
L2  
AC  
internal  
fuse  
L
N
Fuse  
L3  
PE  
DC  
22.12.USE IN A TIGHTLY SEALED ENCLOSURE  
When the power supply is installed in a tightly sealed enclosure, the temperature inside the enclosure will be higher  
than outside. In such situations, the inside temperature defines the ambient temperature for the power supply.  
The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure.  
The power supply is placed in the middle of the box, no other heat producing items are inside the box  
Enclosure:  
Load:  
Input:  
Rittal Typ IP66 Box PK 9522 100, plastic, 254x180x165mm  
24V, 16A; (=80%) load is placed outside the box  
230Vac  
Temperature inside enclosure:  
49.2°C (in the middle of the right side of the power supply with a distance of 2cm)  
Temperature outside enclosure: 24.4°C  
Temperature rise:  
24.8K  
Oct. 2013 / Rev. 2.2 DS-QS20.241-EN  
All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.  
25/26  