24V, 20A, SINGLE PHASE INPUT  
18. DIELECTRIC STRENGTH  
The output voltage is floating and has no ohmic connection to the ground. Type and factory tests are conducted by  
the manufacturer. Field tests may be conducted in the field using the appropriate test equipment which applies the  
voltage with a slow ramp (2s up and 2s down). Connect all input-terminals together as well as all output poles before  
conducting the test. When testing, set the cut-off current settings to the value in the table below.  
Fig. 18-1 Dielectric strength  
A
B
C
D
Type test  
Factory test  
Field test  
60s  
5s  
2500Vac 3000Vac  
2500Vac 2500Vac  
2000Vac 2000Vac  
500Vac  
500Vac  
500Vac  
> 40mA  
500Vac  
500Vac  
500Vac  
> 1mA  
Input  
DC-ok  
B*)  
L
N
5s  
Cut-off current setting > 15mA  
> 15mA  
A
D
To fulfil the PELV requirements according to EN60204-1 § 6.4.1, we  
recommend that either the + pole, the – pole or any other part of  
the output circuit shall be connected to the protective earth  
system. This helps to avoid situations in which a load starts  
unexpectedly or can not be switched off when unnoticed earth  
faults occur.  
Output  
Earth, PE  
C
+
-
B*) When testing input to DC-OK ensure that the max. voltage between DC-OK and the output is not exceeded (column D). We recommend  
connecting DC-OK pins and the output pins together when performing the test.  
Oct. 2013 / Rev. 2.2 DS-QS20.241-EN  
All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.  
16/26  
www.pulspower.com Phone +49 89 9278 0 Germany  
 
 