Q-Series  
24V, 20A, SINGLE PHASE INPUT  
19. APPROVALS  
EC Declaration of Conformity  
The CE mark indicates conformance with the  
- EMC directive 2004/108/EC,  
- Low-voltage directive (LVD) 2006/95/EC,  
- RoHS directive 2011/65/EU and the  
- ATEX directive 94/9/EC (only for QS20.241-A1)  
IEC 60950-1  
2nd Edition  
CB Scheme,  
Information Technology Equipment  
UL 508  
Listed for use as Industrial Control Equipment;  
U.S.A. (UL 508) and Canada (C22.2 No. 107-1-01);  
IND. CONT. EQ.  
E-File: E198865  
UL 60950-1  
2nd Edition  
Recognized for use as Information Technology Equipment,  
Level 5; U.S.A. (UL 60950-1) and Canada (C22.2 No. 60950-1);  
E-File: E137006  
Applicable for altitudes up to 2000m.  
ANSI / ISA 12.12.01-2007  
(Class I Div 2)  
Recognized for use in Hazardous Location Class I Div 2 T3  
Groups A,B,C,D systems; U.S.A. (ANSI / ISA 12.12.01-2007) and  
Canada (C22.2 No. 213-M1987)  
EN 60079-15  
ATEX  
(QS20.241-A1 only)  
Suitable for use in Class 1 Zone 2 Groups IIa, IIb and IIc  
locations. Number of ATEX certificate: EPS 09 ATEX 1 236 X  
The power supply must be built-in in an IP54 enclosure.  
II 3G Ex nA nC II T3 Gc  
Marine  
GL (Germanischer Lloyd) classified and  
ABS (American Bureau for Shipping) PDA  
Environmental category: C, EMC2  
Marine and offshore applications  
SEMI F47  
GOST P  
SEMI F47-0706  
Ride-through compliance for semiconductor industry.  
Full SEMI range compliance  
(Input: AC120V or higher, output: < 480W)  
Certificate of Conformity for Russia and other GUS countries  
Oct. 2013 / Rev. 2.2 DS-QS20.241-EN  
All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.  
17/26  
www.pulspower.com Phone +49 89 9278 0 Germany  
 