QS20.241, QS20.241-A1, QS20.241-C1
Q-Series
24V, 20A, SINGLE PHASE INPUT
16. PROTECTION FEATURES
Output protection
Electronically protected against overload, no-load and short-circuits *)
Output over-voltage protection
typ. 32Vdc
max. 37Vdc
In case of an internal power supply defect, a redundant
circuit limits the maximum output voltage. The output
shuts down and automatically attempts to restart.
Degree of protection
IP 20
EN/IEC 60529
Penetration protection
Over-temperature protection
Input transient protection
Internal input fuse
> 3.5mm / > 5mm
yes
top side / bottom side; e.g. screws, small parts
Output shut-down with automatic restart
MOV (Metal Oxide Varistor)
included
not user replaceable
*) In case of a protection event, audible noise may occur.
17. SAFETY FEATURES
Input / output separation *)
SELV
PELV
IEC/EN 60950-1
IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41
double or reinforced insulation
Class of protection
I
PE (Protective Earth) connection required
Isolation resistance
PE resistance
> 5MOhm
< 0.1Ohm
input to output, 500Vdc
Touch current (leakage current)
typ. 0.23mA / 0.63mA
typ. 0.34mA / 0.93mA
typ. 0.58mA / 1.56mA
< 0.31mA / 0.77mA
< 0.45mA / 1.13mA
< 0.80mA / 2.00mA
100Vac, 50Hz, TN-,TT-mains / IT-mains
120Vac, 60Hz, TN-,TT-mains / IT-mains
230Vac, 50Hz, TN-,TT-mains / IT-mains
110Vac, 50Hz, TN-,TT-mains / IT-mains
132Vac, 60Hz, TN-,TT-mains / IT-mains
264Vac, 50Hz, TN-,TT-mains / IT-mains
*) double or reinforced insulation
Oct. 2013 / Rev. 2.2 DS-QS20.241-EN
All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
15/26
www.pulspower.com Phone +49 89 9278 0 Germany