QS20.241, QS20.241-A1, QS20.241-C1  
Q-Series  
24V, 20A, SINGLE PHASE INPUT  
13. FRONT SIDE AND USER ELEMENTS  
Fig. 13-1 Front side  
A
B
Input Terminals (Quick-connect spring-clamp terminals)  
N, L  
Line input  
PE (Protective Earth) input  
Output Terminals (Quick-connect spring-clamp terminals, two pins  
per pole)  
+
Positive output  
Negative (return) output  
C
DC-OK Relay Contact (Quick-connect spring-clamp terminals)  
The DC-OK relay contact is synchronized with the DC-OK LED.  
See chapter 8 for details.  
D Output voltage potentiometer  
Open the flap to adjust the output voltage. Factory set: 24.1V  
E
F
DC-OK LED (green)  
On, when the output voltage is >90% of the adjusted output voltage  
Overload LED (red)  
On, when the voltage on the output terminals is <90% of the  
adjusted output voltage, or in case of a short circuit in the output.  
Input voltage is required.  
Indicators, LEDs  
Overload LED  
DC-OK LED  
ON  
ON  
DC-OK Contact  
Closed  
Closed  
Normal mode  
OFF  
OFF  
*)  
During BonusPower®  
Overload (VOUT < 90%)  
Output short circuit  
Temperature Shut-down  
No input power  
OFF  
Open  
*)  
*)  
OFF  
OFF  
OFF  
OFF  
Open  
Open  
Open  
*) Up to 4s of overloading, the power supply delivers continuous output current. After this, the output power is reduced to nearly zero for  
approx. 17s before a new start attempt is automatically performed. If the overload has been cleared, the device will operate normally. If the  
overload still exists, the output current will be delivered for 2 to 4s (depending on the overload) again followed by a 17s rest time. This cycle  
is repeated as long as the overload exists.  
The red overload LED is permanently on when the overload current is continuously flowing. During the 17s rest period, the red LED is  
flashing with a frequency of approx. 1.3Hz.  
Oct. 2013 / Rev. 2.2 DS-QS20.241-EN  
All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.  
12/26  