QS20.241, QS20.241-A1, QS20.241-C1  
Q-Series  
24V, 20A, SINGLE PHASE INPUT  
7. HOLD-UP TIME  
AC 100V  
64ms  
32ms  
AC 120V  
64ms  
32ms  
AC 230V  
99ms  
51ms  
Hold-up Time  
typ.  
typ.  
at 24V, 10A, see Fig. 7-1  
at 24V, 20A, see Fig. 7-1  
Fig. 7-1 Hold-up time vs. input voltage  
Fig. 7-2 Shut-down behavior, definitions  
Hold-up  
Time  
100ms  
Zero Transition  
90  
80  
70  
60  
50  
40  
30  
20  
10  
Input  
Voltage  
- 5%  
Output  
Voltage  
Hold-up Time  
Input Voltage  
155 190 230Vac  
85  
120  
8. DC-OK RELAY CONTACT  
This feature monitors the output voltage, which is produced by the power supply itself. It is independent of a back-fed  
voltage from a unit connected in parallel to the power supply output.  
Contact closes  
Contact opens  
As soon as the output voltage reaches the adjusted output voltage level.  
As soon as the output voltage dips more than 10% below the adjusted output voltage.  
Short dips will be extended to a signal length of 250ms. Dips shorter than 1ms will be ignored.  
Contact re-closes  
Contact ratings  
As soon as the output voltage exceeds 90% of the adjusted voltage.  
max  
min  
60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A  
1mA at 5Vdc  
resistive load  
min. permissible load  
Isolation voltage  
See dielectric strength table in section 18.  
Fig. 8-1 DC-ok relay contact behavior  
VOUT = VADJ  
0.9* VADJ  
10%  
<
>
250ms  
1ms  
1ms  
open  
closed  
open  
closed  
Note: The DC-ok feature requires that the output voltage reaches the nominal (=adjusted) level after turn-on in order to function according  
to specification. If this level cannot be achieved, the overload lamp will be on and the DC-ok contact will be open. The overload signal  
will only shut off as soon as the adjusted voltage is reached. This is an important condition to consider particularly, if the load is a  
battery, the power supply is used in parallel or the power supply is used for N+1 redundant systems.  
Oct. 2013 / Rev. 2.2 DS-QS20.241-EN  
All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.  
8/26  