K3HB-V
Specifications
■ Ratings
Power supply voltage
100 to 240 VAC (50/60 Hz), 24 VAC/VDC, DeviceNet power supply: 24 VDC
Allowable power supply voltage range
85% to 110% of the rated power supply voltage, DeviceNet power supply: 11 to 25 VDC
Power consumption
(See note 1.)
100 to 240 V: 18 VA max. (max. load)
24 VAC/DC: 11 VA/7 W max. (max. load)
Current consumption
Input
DeviceNet power supply: 50 mA max. (24 VDC)
DC voltage
A/D conversion method
External power supply
Delta-Sigma method
10 VDC ±5%, 100 mA (models with external power supply only) or 5 VDC, 100 mA (models with external
power supply only)
Event inputs
(See note 2.)
Timing input
NPN open collector or no-voltage contact signal
ON residual voltage: 3 V max.
ON current at 0 Ω: 17 mA max.
Max. applied voltage: 30 VDC max.
OFF leakage current: 1.5 mA max.
Startup compensation
timer input
NPN open collector or no-voltage contact signal
ON residual voltage: 2 V max.
ON current at 0 Ω: 4 mA max.
Max. applied voltage: 30 VDC max.
OFF leakage current: 0.1 mA max.
Hold input
Reset input
Forced-zero input
Bank input
Output ratings (depends Relay output
on the model)
250 VAC, 30 VDC, 5 A (resistive load)
Mechanical life expectancy: 5,000,000 operations, Electrical life expectancy: 100,000 operations
Transistor output
Linear output
Maximum load voltage: 24 VDC, Maximum load current: 50 mA, Leakage current: 100 µA max.
Linear output 0 to 20 mA DC, 4 to 20 mA DC:
Load: 500 Ω max, Resolution: Approx. 10,000, Output error: ±0.5% FS
Linear output 0 to 5 VDC, 1 to 5 VDC, 0 to 10 VDC:
Load: 5 kΩ max, Resolution: Approx. 10,000, Output error: ±0.5% FS
(1 V or less: ±0.15 V; no output for 0 V or less)
Display method
Main functions
Negative LCD (backlit LED) display
7-segment digital display (Character height: PV: 14.2 mm (green/red); SV: 4.9 mm (green)
Scaling function, measurement operation selection, averaging, previous average value comparison, forced-
zero, zero-limit, output hysteresis, output OFF delay, output test, teaching, display value selection, display
color selection, key protection, bank selection, display refresh period, maximum/minimum hold, reset
Ambient operating temperature
Ambient operating humidity
Storage temperature
Altitude
−10 to 55°C (with no icing or condensation)
25% to 85%
−25 to 65°C (with no icing or condensation)
2,000 m max.
Accessories
Watertight packing, 2 fixtures, terminal cover, unit stickers, operation manual. DeviceNet models also include
a DeviceNet connector (Hirose HR31-5.08P-5SC(01)) and crimp terminals (Hirose HR31-SC-121) (See note
3.)
Note: 1. DC power supply models require a control power supply capacity of approximately 1 A per Unit when power is turned ON. Particular attention is required
when using two or more DC power supply models. The OMRON S8VS-series DC Power Supply Unit is recommended.
2. PNP input types are also available.
3. For K3HB-series DeviceNet models, use only the DeviceNet Connector included with the product. The crimp terminals provided are for Thin Cables.
2