 浏览型号EBDW020A0B41-HZ的Datasheet PDF文件第13页浏览型号EBDW020A0B41-HZ的Datasheet PDF文件第14页浏览型号EBDW020A0B41-HZ的Datasheet PDF文件第15页浏览型号EBDW020A0B41-HZ的Datasheet PDF文件第16页浏览型号EBDW020A0B41-HZ的Datasheet PDF文件第18页浏览型号EBDW020A0B41-HZ的Datasheet PDF文件第19页浏览型号EBDW020A0B41-HZ的Datasheet PDF文件第20页浏览型号EBDW020A0B41-HZ的Datasheet PDF文件第21页  
Data Sheet  
GE  
EBDW020A0B Barracuda™ Series; DC-DC Converter Power Modules  
36-75Vdc Input; 12.0Vdc, 20.0A, 240W Output  
Both 100kHz and 400kHz bus speeds are supported by the  
module. Connection for the PMBus interface should follow  
the High Power DC specifications given in section 3.1.3 in the  
SMBus specification V2.0 for the 400kHz bus speed or the  
Low Power DC specifications in section 3.1.2. The complete  
SMBus specification is available from the SMBus web site,  
smbus.org.  
PU: Factory set to 1. EBDW025A0B requires On/Off(i) pin to  
be connected to proper input rail for module to power up.  
This bit is used together with the CMD, CPR and ON bits to  
determine startup.  
Bit Value  
Action  
Module does not power up until commanded  
by the analog ON/OFF pin and the OPERATION  
command as programmed in bits [2:0] of the  
ON_OFF_CONFIG register.  
1
PMBus Data Format  
For commands that set or report any voltage thresholds  
related to output voltage (including VOUT_COMMAND,  
VOUT_MARGIN, POWER_GOOD and READ_VOUT), the module  
supports the linear data format consisting of a two byte  
value with a 16-bit, unsigned mantissa, and a fixed exponent  
of -12. The format of the two data bytes is shown below:  
CMD: The CMD bit controls how the device responds to the  
OPERATION command.  
Bit Value  
Action  
Module ignores the ON bit in the OPERATION  
command  
0
Module responds to the ON bit in the  
OPERATION command  
1
CPR: Factory set to 1. EBDW025A0B requires On/Off(i) pin to  
be connected to proper input rail for module to power up.  
This bit is used together with the CMD and ON bits to  
determine startup.  
Bit Value  
Action  
The value of the number is then given by  
Value = Mantissa x 2-12  
Module requires the analog ON/OFF pin to be  
asserted to start the unit  
1
For commands that set all other thresholds, voltages or  
report such quantities, the module supports the linear data  
format consisting of a two byte value with an 11-bit, two’s  
complement mantissa and a 5-bit, two’s complement  
exponent. The format of the two data bytes is shown below:  
PMBus Adjustable Input Undervoltage Lockout  
The module allows adjustment of the input under voltage  
lockout and hysteresis. The command VIN_ON allows setting  
the input voltage turn on threshold, while the VIN_OFF  
command sets the input voltage turn off threshold. For both  
the VIN_ON and VIN_OFF commands, possible values range  
from 32.000 to 46.000V in 0.125V steps. VIN_ON must be  
2.000V greater than VIN_OFF.  
Both the VIN_ON and VIN_OFF commands use the “Linear”  
format with two data bytes. The upper five bits [7:3] of the  
high data byte form the two’s complement representation of  
the exponent, which is fixed at –3 (decimal). The remaining 11  
bits are used for two’s complement representation of the  
mantissa, with the 11th bit fixed at zero since only positive  
numbers are valid. The data associated with VIN_ON and  
VIN_OFF can be stored to non-volatile memory using the  
STORE_DEFAULT_ALL command.  
The value is of the number is then given by  
Value = Mantissa x 2 Exponent  
PMBus Enabled On/Off  
The module can also be turned on and off via the PMBus  
interface. The OPERATION command is used to actually turn  
the module on and off via the PMBus, while the  
ON_OFF_CONFIG command configures the combination of  
analog ON/OFF pin input and PMBus commands needed to  
turn the module on and off. Bit [7] in the OPERATION  
command data byte enables the module, with the following  
functions:  
PMBus Adjustable Soft Start Delay and Rise Time  
The soft start delay and rise time can be adjusted in the  
module via PMBus. The TON_DELAY command sets the delay  
time in ms, and allows choosing delay times between 10ms  
and 500ms, with resolution of 0.5ms. The TON_RISE  
command sets the rise time in ms, and allows choosing soft  
start times between 15ms and 500ms, with resolution of  
0.5ms. When setting TON_RISE, make sure that the charging  
current for output capacitors can be delivered by the module  
in addition to any load current to avoid nuisance tripping of  
the overcurrent protection circuitry during startup. Both the  
TON_RISE and TON_DELAY commands use the “Linear”  
format with two data bytes. The upper five bits [7:3] of the  
high data byte form the two’s complement representation of  
the exponent, which is fixed at –1 (decimal). The remaining 11  
0
1
:
:
Output is disabled  
Output is enabled  
This module uses the lower five bits of the ON_OFF_CONFIG  
data byte to set various ON/OFF options as follows:  
Bit Position  
Access  
4
r
3
r/w  
2
r
1
r
POL  
1
0
r
CPA  
1
Function  
Default Value  
PU  
1
CMD CPR  
1
1
April 15, 2013  
©2012 General Electric Company. All rights reserved.  
Page 17  