Data Sheet
GE
CP2000AC54TE CPL High Efficiency Rectifier
100-120/200-277VAC input; Default Outputs: ±54VDC @ 2000W, 5VDC @ 4W
Table 1: FRU_ID
The upper quarter of memory starting from address 6144 shall be reserved for factory ID and factory data.
Memory Memory Length Format
Location Location (bytes)
Static
Value
Type
Fixed
Fixed
Variable
Variable
Variable
Description
Notes/Example
Decimal
6144d
6156d
6166d
6172d
6178d
(HEX)
0x1800
0x180C
0x1816
0x181C
0x1822
12
10
6
6
14
ASCII
ASCII
ASCII
ASCII
ASCII
GE-energy - Product ID
GE-energy – Part Number
GE-energy - Hardware revision
spare
CP2000AC54TE
123456789x or C123456789
x:xxxx controlled by PDI series #
GE-energy - Serial_No
01KZ51018193xx
01 …. Year of manufacture - 2001
KZ … factory, in this case Matamoros
51 .. week of manufacture
______018193xx serial # mfg choice
6192d
6232d
6240d
6242d
0x1830
0x1858
0x1860
0x1862
40
8
2
ASCII
ASCII
HEX
Variable
Fixed
Fixed
GE- Manufacturing location
spare
spare
“Matamoros, Tamps, Mexico”
158
ASCII
Fixed
Customer Information
These fields are reserved for use by the
customer.
6400d
6405d
6410d
6415d
6420d
6425d
6430d
6431d
6436d
6441d
6446d
0x1900
0x1905
0x190A
0x190F
0x1914
0x1919
0x191E
9x191F
0x1924
0x1929
0 x 192E
5
5
5
5
5
5
1
5
5
5
5
HEX
HEX
HEX
HEX
HEX
HEX
HEX
HEX
HEX
HEX
HEX
Fixed
Fixed
Fixed
Fixed
Fixed
Fixed
Variable
Fixed
Fixed
Fixed
Fixed
M, B, & R for voltage read
M, B, & R for current read
M, B, & R temp read
spare
M, B, & R for voltage set
M, B, & R for input voltage read
Validation CHKSUM
M, B, & R for input power read
M, B, & R for fan percent adjust
M, B, & R for fan RPM read
M, B, & R for converter input
voltage read
M & B are 2 bytes each sent as MSB and then
LSB. R is one byte. These are stored as two’s
complement.
See the section on Direct Mode Constants
Stored in the EEPROM for the constants stored
in these fields
Notes:
CHkSUM is a CRC-8 calculation from location 0x1800 to location 0x19FF without including serial number and checksum locations. chksum_value =
0xFF - (mask of SUM with 0x0000ff) write chksum_value byte to location 0x191E.
Table 2: Alarm and LED state summary
Power Supply LED State
Monitoring Signals
AC OK
Green
1
DC OK
Green
1
Service
Amber
0
Fault
Red
0
Module
Present
LO
Condition
Fault
HI
OTW
HI
PFW
HI
OK
Thermal Alarm (5C before shutdown)
Thermal Shutdown
1
1
1
1
0
0
0
0
0
0
0
0
0
1
1
1
0
0
1
1
0
1
HI
LO
LO
HI
HI
LO
LO
LO
LO
LO
LO
LO
LO
LO
LO
HI
1
0
LO
LO
LO
HI
LO
LO
LO
LO
LO
LO
Defective Fan
1
0
Blown AC Fuse in Unit
AC Present but not within limits
AC not present1
1
0
HI
Blinks
0
HI
0
1
1
1
1
0
HI
HI
Boost Stage Failure
0
0
LO
HI
Over Voltage Latched Shutdown
LO
HI
HI
HI
HI
LO
LO
HI
Over Current
Blinks
1
Non-catastrophic Internal Failure2
Missing Module
LO
Standby (remote)
1
1
1
0
1
1
0
Blinks
0
0
0
HI
HI
HI
HI
HI
HI
LO
HI
HI
LO
LO
LO
Service Request (PMBus mode)
Communications Fault (RS485 mode)
1
Blinks
This signal is correct if the rectifier is back biased from other rectifiers in the shelf .
2 Any detectable fault condition that does not cause a shutting down. For example, ORing FET failure, boost section out of regulation, etc.
3
Signal transition from HI to LO is output load dependent
August 16, 2013
©2013 General Electric Company. All rights reserved.
Page 17