Data Sheet  
GE  
CP2000AC54TE CPL High Efficiency Rectifier  
100-120/200-277VAC input; Default Outputs: ±54VDC @ 2000W, 5VDC @ 4W  
Table 1: FRU_ID  
The upper quarter of memory starting from address 6144 shall be reserved for factory ID and factory data.  
Memory Memory Length Format  
Location Location (bytes)  
Static  
Value  
Type  
Fixed  
Fixed  
Variable  
Variable  
Variable  
Description  
Notes/Example  
Decimal  
6144d  
6156d  
6166d  
6172d  
6178d  
(HEX)  
0x1800  
0x180C  
0x1816  
0x181C  
0x1822  
12  
10  
6
6
14  
ASCII  
ASCII  
ASCII  
ASCII  
ASCII  
GE-energy - Product ID  
GE-energy – Part Number  
GE-energy - Hardware revision  
spare  
CP2000AC54TE  
123456789x or C123456789  
x:xxxx controlled by PDI series #  
GE-energy - Serial_No  
01KZ51018193xx  
01 …. Year of manufacture - 2001  
KZ … factory, in this case Matamoros  
51 .. week of manufacture  
______018193xx serial # mfg choice  
6192d  
6232d  
6240d  
6242d  
0x1830  
0x1858  
0x1860  
0x1862  
40  
8
2
ASCII  
ASCII  
HEX  
Variable  
Fixed  
Fixed  
GE- Manufacturing location  
spare  
spare  
“Matamoros, Tamps, Mexico”  
158  
ASCII  
Fixed  
Customer Information  
These fields are reserved for use by the  
customer.  
6400d  
6405d  
6410d  
6415d  
6420d  
6425d  
6430d  
6431d  
6436d  
6441d  
6446d  
0x1900  
0x1905  
0x190A  
0x190F  
0x1914  
0x1919  
0x191E  
9x191F  
0x1924  
0x1929  
0 x 192E  
5
5
5
5
5
5
1
5
5
5
5
HEX  
HEX  
HEX  
HEX  
HEX  
HEX  
HEX  
HEX  
HEX  
HEX  
HEX  
Fixed  
Fixed  
Fixed  
Fixed  
Fixed  
Fixed  
Variable  
Fixed  
Fixed  
Fixed  
Fixed  
M, B, & R for voltage read  
M, B, & R for current read  
M, B, & R temp read  
spare  
M, B, & R for voltage set  
M, B, & R for input voltage read  
Validation CHKSUM  
M, B, & R for input power read  
M, B, & R for fan percent adjust  
M, B, & R for fan RPM read  
M, B, & R for converter input  
voltage read  
M & B are 2 bytes each sent as MSB and then  
LSB. R is one byte. These are stored as two’s  
complement.  
See the section on Direct Mode Constants  
Stored in the EEPROM for the constants stored  
in these fields  
Notes:  
CHkSUM is a CRC-8 calculation from location 0x1800 to location 0x19FF without including serial number and checksum locations. chksum_value =  
0xFF - (mask of SUM with 0x0000ff) write chksum_value byte to location 0x191E.  
Table 2: Alarm and LED state summary  
Power Supply LED State  
Monitoring Signals  
AC OK  
Green  
1
DC OK  
Green  
1
Service  
Amber  
0
Fault  
Red  
0
Module  
Present  
LO  
Condition  
Fault  
HI  
OTW  
HI  
PFW  
HI  
OK  
Thermal Alarm (5C before shutdown)  
Thermal Shutdown  
1
1
1
1
0
0
0
0
0
0
0
0
0
1
1
1
0
0
1
1
0
1
HI  
LO  
LO  
HI  
HI  
LO  
LO  
LO  
LO  
LO  
LO  
LO  
LO  
LO  
LO  
HI  
1
0
LO  
LO  
LO  
HI  
LO  
LO  
LO  
LO  
LO  
LO  
Defective Fan  
1
0
Blown AC Fuse in Unit  
AC Present but not within limits  
AC not present1  
1
0
HI  
Blinks  
0
HI  
0
1
1
1
1
0
HI  
HI  
Boost Stage Failure  
0
0
LO  
HI  
Over Voltage Latched Shutdown  
LO  
HI  
HI  
HI  
HI  
LO  
LO  
HI  
Over Current  
Blinks  
1
Non-catastrophic Internal Failure2  
Missing Module  
LO  
Standby (remote)  
1
1
1
0
1
1
0
Blinks  
0
0
0
HI  
HI  
HI  
HI  
HI  
HI  
LO  
HI  
HI  
LO  
LO  
LO  
Service Request (PMBus mode)  
Communications Fault (RS485 mode)  
1
Blinks  
This signal is correct if the rectifier is back biased from other rectifiers in the shelf .  
2 Any detectable fault condition that does not cause a shutting down. For example, ORing FET failure, boost section out of regulation, etc.  
3
Signal transition from HI to LO is output load dependent  
August 16, 2013  
©2013 General Electric Company. All rights reserved.  
Page 17  