Data Sheet  
GE  
CP2000AC54TE CPL High Efficiency Rectifier  
100-120/200-277VAC input; Default Outputs: ±54VDC @ 2000W, 5VDC @ 4W  
Read input string (DCh) : Reads back the input voltage and  
input power consumed by the power supply. In order to  
improve the resolution of the input voltage reading the data is  
shifted by 75V.  
reduce the fan speed below what the power supply requires  
for internal control.  
Fan_normal_speed (E0h): This command returns fan control  
to the power supply. It does not require a trailing data byte.  
1
S
7
1
Wr  
1
A
8
Read_Fan_speed (E1h) : Returns the commanded fan speed in  
percent and the measured fan speed in RPM from the  
individual fans. Up to 3 fans are supported. If a fan does not  
exist (units may contain from 1 to 3 fans), or if the command is  
not supported the unit return 0x00.  
Slave address  
Command Code 0xDC  
1
A
1
Sr  
7
1
Rd  
1
A
Slave Address  
8
1
A
8
1
A
Byte Count = 4  
Voltage  
1
S
8
1
A
8
1
A
Slave address  
Wr  
Command 0xE1  
8
1
A
8
1
A
8
PEC  
1
1
P
Power - LSB  
Power - MSB  
No-ack  
1
8
1
8
1
Sr  
Slave address  
Rd  
A
Byte count = 5  
A
Read_firmware_rev [0 x DD]: Reads back the firmware  
revision of all three µC in the power supply.  
8
1
A
8
1
A
8
1
A
8
1
A
Adjustment %  
Fan-1  
Fan-2  
Fan-3  
1
S
7
1
Wr  
1
A
8
1
A
8
PEC  
1
NA  
1
P
Slave address  
Command Code 0xDD  
1
A
1
Sr  
7
1
Rd  
1
A
8
1
A
Stretch_LO_25ms (E2h) : Command used for production test  
of the clock stretch feature.  
Slave Address  
Byte Count = 4  
8
1
A
8
1
A
None supported commands or invalid data: The power  
supply notifies the MASTER if a non-supported command has  
been sent or invalid data has been received. Notification is  
implemented by setting the appropriate STATUS and ALARM  
registers and setting the SMBAlert# flag.  
Primary micro revision  
DSP revision  
8
1
A
8
PEC  
1
1
P
I2c Micro revision  
No-ack  
For example; the read returns one byte for each device (i.e. 0 x  
002114h ). The sequence is primary micro, DSP, and I2C micro.  
0x00 in the first byte indicates that revision information for the  
primary micro is not supported. The number 21 for the DSP  
indicates revision 2.1, and the number 14 for the i2c micro  
indicates revision 1.4.  
Fault Management  
The power supply records faults in the STATUS and ALARM  
registers above and notifies the MASTER controller as  
described in the Alarm Notification section of the non-  
conforming event.  
The STATUS and ALARM registers are continuously updated  
with the latest event registered by the rectifier monitoring  
circuits. A host responding to an SMBusALERT# signal may  
receive a different state of the rectifier if the state has changed  
from the time the SMBusALERT# has been triggered by the  
rectifier.  
Read_run_timer [0 x DE]: This command reads back the  
recorded operational ON state of the power supply in hours.  
The operational ON state is accumulated from the time the  
power supply is initially programmed at the factory. The power  
supply is in the operational ON state both when in standby and  
when it delivers main output power. Recorded capacity is  
approximately 10 years of operational state.  
The power supply differentiates between internal faults that  
are within the power supply and external faults that the  
power supply protects itself from, such as overload or input  
voltage out of limits. The FAULT LED, FAULT PIN or i2c alarm is  
not asserted for EXTERNAL FAULTS. Every attempt is made to  
annunciate External Faults. Some of these annunciations can  
be observed by looking at the input LEDs. These fault  
categorizations are predictive in nature and therefore there is  
a likelihood that a categorization may not have been made  
correctly.  
1
S
7
1
1
A
8
1
A
Slave address Wr  
Command Code 0xDE  
1
Sr  
7
1
Rd  
1
A
8
1
A
Slave Address  
Byte count = 4  
8
1
8
1
8
1
Time - LSB  
A
Time  
A
Time - MSB  
A
Input voltage out of range: The Input LED will continue  
blinking as long as sufficient power is available to power the  
LED. If the input voltage is completely gone the Input LED is  
OFF.  
8
PEC  
1
1
P
No-ack  
Fan_speed_set (DFh) : This command instructs the power  
supply to increase the speed of the fan. The transmitted data  
byte represents the hex equivalent of the duty cycle in  
percentage, i.e. 100% = 0 x 64h. The command can only  
increase fan speed, it cannot instruct the power supply to  
August 16, 2013  
©2013 General Electric Company. All rights reserved.  
Page 15  