Data Sheet  
GE  
CP2000AC54TE CPL High Efficiency Rectifier  
100-120/200-277VAC input; Default Outputs: ±54VDC @ 2000W, 5VDC @ 4W  
Restart after a lachoff: To restart after a latch_off either of  
Alarm-1  
four restart mechanisms are available. The hardware pin  
Enable may be turned OFF and then ON. The unit may be  
commanded to restart via i2c through the Operation  
command by first turning OFF then turning ON . The third way  
to restart is to remove and reinsert the unit. The fourth way is  
to turn OFF and then turn ON ac power to the unit. The fifth  
way is by changing firmware from latch off to restart. Each of  
these commands must keep the power supply in the OFF state  
for at least 2 seconds, with the exception of changing to  
restart.  
Bit  
Title  
Description  
7
Unit in power limit  
An overload condition that results in  
constant power  
6
Primary fault  
Indicates either primary failure or  
INPUT not present. Used in  
conjunction with bit-0 and Status_1  
bits 2 and 5 to assess the fault.  
One of the over_temperature  
sensors tripped the supply  
5
4
3
2
1
Over temp.  
shutdown  
Over temp warning Temperature is too high, close to  
shutdown  
In over current  
A successful restart shall clear all alarm registers, set the  
restarted successful bit of the Status_2 register.  
Shutdown is triggered by low  
output voltage < 39VDC  
.
A power system that is comprised of a number of power  
supplies could have difficulty restarting after a shutdown event  
because of the non-synchronized behavior of the individual  
power supplies. Implementing the latch-off mechanism  
permits a synchronized restart that guarantees the  
simultaneous restart of the entire system.  
Over voltage  
shutdown  
Vout out_of_limits  
Indication the output is not within  
design limits. This condition may or  
may not cause an output shutdown.  
The input voltage is outside design  
limits  
0
Vin out_of_limits  
A synchronous restart can be implemented by;  
1. Issuing a GLOBAL OFF and then ON command to all power  
supplies,  
2. Toggling Off and then ON the ENABLE signal  
3. Removing and reapplying input commercial power to the  
entire system.  
LEDS test ON (D2h) : Will turn-ON simultaneously the four  
front panel LEDs of the Power supply sequentially 7 seconds  
ON and 2 seconds OFF until instructed to turn OFF. The intent  
of this function is to provide visual identification of the power  
supply being talked to and also to visually verify that the LEDs  
operate and driven properly by the micro controller.  
The power supplies should be turned OFF for at least 20 – 30  
seconds in order to discharge all internal bias supplies and  
reset the soft start circuitry of the individual power supplies.  
LEDS test OFF (D3h) : Will turn-OFF simultaneously the four  
front panel LEDs of the Power supply.  
Auto_restart (D9h) : Auto-restart is the default configuration  
for overvoltage, overcurrent and overtemperature shutdowns.  
Service LED ON (D4h) : Requests the power supply to flash-ON  
the Service (ok-to-remove) LED. The flash sequence is  
approximately 0.5 seconds ON and 0.5 seconds OFF.  
However, overvoltage has a unique limitation. An overvoltage  
shutdown is followed by three attempted restarts, each restart  
delayed 1 second, within a 1 minute window. If within the 1  
minute window three attempted restarts failed, the unit will  
latch OFF. If within the 1 minute less than 3 shutdowns  
occurred then the count for latch OFF resets and the 1 minute  
window starts all over again.  
Service LED OFF (D5h) : Requests the power supply to turn OFF  
the Service (ok-to-remove) LED.  
Enable write (D6h) : This command enables write permissions  
into the upper ¼ of memory locations for the external  
EEPROM. A write into these locations is normally disabled until  
commanded through I2C to permit writing into the protected  
area. A delay of about 10ms is required from the time the  
instruction is requested to the time that the power supply  
actually completes the instruction.  
This command resets the power supply into the default auto-  
restart configuration.  
Isolation test (DAh): This command verifies functioning of  
output OR’ing. At least two paralleled power supplies are  
required. The host should verify that N+1 redundancy is  
established. If N+1 redundancy is not established the test can  
fail. Only one power supply should be tested at a time.  
See the FRU-ID section for further information of content  
written into the EEPROM at the factory.  
Disable write (D7h) : This command disables write permissions  
into the upper ¼ of memory locations for the external  
EEPROM.  
Verifying test completion should be delayed for approximately  
30 seconds to allow the power supply sufficient time to  
properly execute the test.  
Unit in Power Limit or in Current Limit: When output voltage  
is > 36VDC the Output LED will continue blinking.  
When output voltage is < 36VDC, if the unit is in the RESTART  
mode, it goes into a hiccup. When the unit is ON the output  
LED is ON, when the unit is OFF the output LED is OFF.  
Failure of the isolation test is not considered a power supply  
FAULT because the N+1 redundancy requirement cannot be  
verified. The user must determine whether a true isolation fault  
indeed exists.  
When the unit is in latched shutdown the output LED is OFF.  
Inhibit_restart (D8h) : The Inhibit-restart command directs  
the power supply to remain latched off for over_voltage,  
over_temperature and over_current. The command needs to  
be sent to the power supply only once. The power supply will  
remember the INHIBIT instruction as long as internal bias is  
active.  
August 16, 2013  
©2013 General Electric Company. All rights reserved.  
Page 14  