欢迎访问ic37.com |
会员登录 免费注册
发布采购

CAR2012TE 参数 Datasheet PDF下载

CAR2012TE图片预览
型号: CAR2012TE
PDF下载: 下载PDF文件 查看货源
内容描述: [Universal input with PFC Constant power characteristic 2 front panel LEDs: 1-input;2]
分类和应用: 功率因数校正
文件页数/大小: 20 页 / 444 K
品牌: LINEAGEPOWER [ LINEAGE POWER CORPORATION ]
 浏览型号CAR2012TE的Datasheet PDF文件第9页浏览型号CAR2012TE的Datasheet PDF文件第10页浏览型号CAR2012TE的Datasheet PDF文件第11页浏览型号CAR2012TE的Datasheet PDF文件第12页浏览型号CAR2012TE的Datasheet PDF文件第14页浏览型号CAR2012TE的Datasheet PDF文件第15页浏览型号CAR2012TE的Datasheet PDF文件第16页浏览型号CAR2012TE的Datasheet PDF文件第17页  
Data Sheet  
GE  
CAR2012TE series rectifier  
Input: 85Vac to 264Vac; Output: 12 Vdc @ 2000W; 3.3Vdc or 5 Vdc @ 4A  
STATUS_BYTE (0x78) : Returns one byte of information with a  
STATUS_TEMPERATURE (0x7D): Returns one byte of  
summary of the most critical device faults.  
information of temperature related faults.  
Bit  
Position  
7
6
5 - 0  
Default  
Value  
Bit  
Position  
Default  
Value  
Flag  
Flag  
OT Fault  
OT Warning  
Not supported  
0
0
0
7
6
5
4
3
2
1
0
Busy  
OFF  
VOUT Overvoltage  
IOUT Overcurrent  
VIN Undervoltage  
Temperature  
0
0
0
0
0
0
0
0
STATUS_CML (0x7E): Returns one byte of information of  
communication related faults.  
Bit  
Position  
CML (Comm. Memory Fault)  
None of the above  
Default  
Value  
Flag  
7
6
5
4 - 2  
1
0
Invalid/Unsupported Command  
Invalid/Unsupported Data  
Packet Error Check Failed  
Not supported  
Other Communication Fault  
Not supported  
0
0
0
0
0
0
STATUS_WORD (0x79): Returns status_byte as the low byte  
and the following high_byte.  
Bit  
Position  
Default  
Value  
Flag  
7
6
5
4
3
2
1
0
VOUT fault or warning  
IOUT fault or warning  
INPUT  
0
0
0
0
0
0
0
0
MFR SPECIFIC  
nPOWER_GOOD  
FANS  
OTHER  
UNKNOWN  
STATUS_FAN_1_2 (0x81) : Returns one byte of information  
with a summary of the most critical device faults.  
Bit  
Position  
7
6
5 - 4  
3
Default  
Value  
Flag  
Fan 1 Fault  
Fan 2 Fault  
Not supported  
0
0
0
0
0
0
STATUS_VOUT (0x7A): Returns one byte of information of  
output voltage related faults.  
Fan 1 speed overwritten  
Fan 2 speed overwritten  
Not supported  
Bit  
Position  
Default  
Value  
Flag  
2
1 - 0  
7
6
5
4
3 - 0  
VOUT OV Fault  
VOUT_OV_WARNING  
VOUT_UV_WARNING  
VOUT UV Fault  
0
0
0
0
0
Read back Descriptions  
Not supported  
Single parameter read back: Functions can be read back one  
at a time using the read_word_protocol with PEC. A  
command is first sent out notifying the slave what function is  
to be read back followed by the data transfer.  
STATUS_IOUT (0x7B): Returns one byte of information of  
output current related faults.  
Bit  
Position  
Default  
Value  
Flag  
Analog data is always transmitted LSB followed by MSB. A NA  
following the PEC byte signifies that the transmission is  
complete and is being terminated by the ‘host’.  
7
6
5
IOUT OC Fault  
Not supported  
IOUT OC Warning  
Not supported  
0
0
0
0
1
S
8
1
A
8
1
A
4- 0  
Slave address  
Wr  
Command Code  
1
8
1
A
STATUS_INPUT (0x7C): Returns one byte of information of  
input voltage related faults.  
Sr Slave address  
Rd  
8
LSB  
1
A
8
MSB  
1
A
8
1
1
P
Bit  
Position  
Default  
Value  
Flag  
PEC NA  
7
6
5
4
3 - 0  
VIN_OV_Fault  
VIN_OV_Warning  
VIN_UV_ Warning  
VIN_UV_Fault  
0
0
0
0
0
Read_fan_speed 1 & 2 (0x90, 0x91): Reading the fan speed is  
in Linear Mode returning the RPM value of the fan.  
Not supported  
February 9, 2014  
©2013 General Electric Company. All rights reserved.  
Page 13