Data Sheet
GE
CAR2012TE series rectifier
Input: 85Vac to 264Vac; Output: 12 Vdc @ 2000W; 3.3Vdc or 5 Vdc @ 4A
Hex
Data
Byte
2
2
The Linear Data Format is a two byte value with an 11-bit,
two’s complement mantissa and a 5-bit, two’s complement
exponent or scaling factor, its format is shown below.
Command
Read_Vout
Code
0x8B
0x8C
0x8D
0x90
0x91
0x97
0x99
0x9A
0x9E
0xD0
0xD1
0xD2
0xD3
0xD4
0xD5
0xD6
Function
Read_Iout
Data Byte High
Data Byte Low
Read_temperature
Read_fan_speed_1
Read_fan_speed_2
Read_Pin
2
Bit
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
2
Exponent (E)
Mantissa (M)
2
The relationship between the Mantissa, Exponent, and Actual
Value (V) is given by the following equation:
2
Mfr_ID
5
V M 2E
Mfr_model
16
15
10
2
CAR2012TEXXXZ01A
01KZ51018193xxx
Mfr_serial
Where:
Read_Std_Parameters
Read_Status_State
Read_Alarm_State
Read_fan_speed
Read_Input_string
Read_mfr_rev
Read_Run_Timer
V is the value
M is the 11-bit, two’s complement mantissa
E is the 5-bit, two’s complement exponent
2
4
Standard features
2
4
Command
Comments
3
ON_OFF_CONFIG
Both the CNTL pin, enabling or disabling
the output, and the OPERATION command
are supported. Other options are not
supported.
EEPROM_record
Test Function
0xD9
0xDF
64
1
Vout_OV_fault_response Only latched (0x80) is supported
CAPABILITY
400KHz, SMBALERT
1.2
PMBus revision
Command Descriptions
PMBusTM Command set:
Operation (0x01) : By default the Power supply is turned ON
at power up as long as Power ON/OFF signal pin is active HI.
The Operation command is used to turn the Power Supply ON
or OFF via the PMBus. The data byte below follows the
OPERATION command.
Non-supported commands are annunciated.
Hex
Code
0x01
0x02
0x03
Data
Command
Operation
ON_OFF_config
Clear_faults
Byte
Function
Output ON/OFF
09, output ON default
Clear Status
1
1
0
Write_protect
0x10
0x12
1
0
Write control
FUNCTION
Unit ON
Unit OFF
DATA BYTE
Restore_default_all
Reset defaults
80
00
Store_default_code
Vout_mode
Vout_command
Fan_command_1
Vout_OV_fault_limit
Vout_OV_warn_limit
Iout_OC_fault_limit
Iout_OC_fault_response4
0x13
0x20
0x21
0x3B
0x40
0x42
0x46
0x47
1
1
2
2
2
2
2
1
Change default state
Vout constants
Set Vout
Set fan speed in %
Set OV fault limit
Set OV warn limit
To RESET the power supply cycle the power supply OFF, wait
at least 2 seconds, and then turn back ON. All alarms and
shutdowns are cleared during a restart.
Clear_faults (0x03): This command clears all STATUS and
FAULT registers and resets the SMBAlert# line.
If a fault still persists after the issuance of the clear_faults
command the specific registers indicating the fault are reset
and the SMBAlert# line is activated again.
Latch or hiccup
Set OC warn limit
Iout_OC_warn_limit
OT_fault_limit
OT_fault_response5
0x4A
0x4F
0x50
2
2
1
Latch or hiccup
Set OT warn limit
OT_warn_limit
Status_byte
Status_word
Status_Vout
0x51
0x78
0x79
0x7A
0x7B
0x7C
0x7D
0x7E
0x81
2
1
2
1
1
1
1
1
1
WRITE_PROTECT register (0x10): Used to control writing to
the PMBus device. The intent of this command is to provide
protection against accidental changes. All supported
command parameters may have their parameters read,
regardless of the write_protect settings. The default setting of
this register is disable_all_writes except write_protect 0x80h.
Status_Iout
Status_input
Status_temperature
Status_CML
FUNCTION
DATA BYTE
Status_fan_1_2
Enable all writes
00
80
40
Read_Iin
0x89
2
Disable all writes except write_protect
Disable all writes except write_protect and
OPERATION
4
Only latched (0xC0) or hiccup (0xF8) are supported
Only latched (0x80) or restart (0xC0) are supported
Restore_Default_All (0x12): Restores all register values and
responses to the default parameters set in the power supply.
5
February 9, 2014
©2013 General Electric Company. All rights reserved.
Page 11