Data Sheet  
GE  
CAR2012TE series rectifier  
Input: 85Vac to 264Vac; Output: 12 Vdc @ 2000W; 3.3Vdc or 5 Vdc @ 4A  
Store_default_code (0x13): Default values desired to be  
overwritten must be executed one at a time. In this fashion  
some protection is offered to ensure that only those values  
that are desired to be changed are in fact changed.  
Vout_OV_warn_limit (0x42): OV_warning is extremely useful  
because it gives the system controller a heads up that the  
output voltage is drifting out of regulation and the power  
supply is close to shutting down. Pre-amative action may be  
taken before the power supply would shut down and  
potentially disable the system. This level can be permanently  
changed and stored in non-volatile memory.  
Vout_mode (0x20): This is a ‘read only’ register. The upper  
three bits specify the supported data format, in this case  
Linear mode. The lower five bits specify the exponent of the  
data being read back in two’s complement binary format for  
output voltage related commands, such as Vout_command.  
These commands have a 16 bit mantissa. The exponent is  
fixed by the module and is returned by this command.  
Iout_OC_fault_limit (0x46): Sets the value at which the power  
supply will shut down. The default OC_fault_limit is 68Adc at  
high_line and 30A at low_line. (The value is contingent on  
whether the power supply operates in the low_line or  
high_line mode). This level can be permanently changed and  
stored in non-volatile memory. Which level is changed is  
contingent on the input voltage applied to the power supply  
at the time the change takes place.  
Mode  
Linear  
Bits [7:5]  
Bits [4:0] (exponent)  
000b  
xxxxxb  
Vout_Command (0x21) : This command is used to change the  
output voltage of the power supply.  
Iout_OC_fault_response (0x47): Sets the response if the  
output overload exceeds the OC_Fault_limit value. The  
default OC_fault_response is hiccup (0xF8). The only two  
allowable states are latched (0xC0) or hiccup. The default  
response state can be permanently changed and stored in  
non-volatile memory. The response is the same for both  
low_line and high_line operations.  
Changing the output voltage should be performed  
simultaneously to all power supplies operating in parallel  
using the Global Address (Broadcast) feature. If only a single  
power supply is instructed to change its output, it may  
attempt to source all the required power which can cause  
either a power limit or shutdown condition.  
Software programming of output voltage permanently  
overrides the set point voltage configured by the Vprog  
signal pin. The program no longer looks at the ‘Vprog pin’ and  
will not respond to any hardware voltage settings. If power is  
removed from the µController it will reset itself into its default  
configuration looking at the Vprog signal for output voltage  
control. In many applications, the Vprog pin is used for  
setting initial conditions, if different that the factory setting.  
Software programming then takes over once I2C  
Iout_OC_warn_limit (0x4A): Sets the value at which the  
power supply issues a warning that the output current is  
getting too close to the shutdown level. The default  
OC_Warn_limit is set to 64.8A at high_line and 27.8A at  
low_line. This level can be permanently changed and stored  
in non-volatile memory. Which level is changed is contingent  
on the input voltage applied to the power supply at the time  
the change takes place.  
communications are established.  
OT_fault_limit (0x4F ): Sets the temperature value at which  
the power supply shuts down. The default OT_fault_limit is  
set at TBDC. This level can be permanently changed and  
stored in non-volatile memory.  
To properly hot-plug a power supply into a live backplane, the  
system generated voltage should get re-configured into  
either the factory adjusted firmware level or the voltage level  
reconfigured by the margin pin. Otherwise, the voltage state  
of the plugged in power supply could be significantly different  
than the powered system.  
OT_fault_response (0x50): Sets the response if the output  
overtemperature exceeds the OT_Fault_limit value. The  
default OT_fault_response is hiccup (0xC0). The only two  
allowable states are latched (0x80) or hiccup. The default  
response state can be permanently changed and stored in  
non-volatile memory.  
Voltage margin range: 10.8Vdc – 13.2 Vdc.  
Fan_command_1 (0x3B): This command instructs the power  
supply to increase the speed of the fan. The transmitted data  
byte represents the hex equivalent of the duty cycle in  
percentage, i.e. 100% = 0 x 64h. The command can only  
increase fan speed, it cannot instruct the power supply to  
reduce the fan speed below what the power supply requires  
for internal control.  
OT_warn_limit (0x51): Sets the value at which the power  
supply issues a warning that internal temperatures are  
getting too close to the shutdown level. The default  
OT_Warn_limit is set to TBDC. This level can be permanently  
changed and stored in non-volatile memory.  
Sending 00h tells the power supply to revert back to its  
internal control.  
Vout_OV_fault_limit (0x40): Sets the value at which the main  
output voltage will shut down. The default OV_fault value is  
set at 60Vdc. This level can be permanently changed and  
stored in non-volatile memory.  
February 9, 2014  
©2013 General Electric Company. All rights reserved.  
Page 12