 浏览型号CS1-B9-14-610-412-BG的Datasheet PDF文件第1页浏览型号CS1-B9-14-610-412-BG的Datasheet PDF文件第2页浏览型号CS1-B9-14-610-412-BG的Datasheet PDF文件第3页浏览型号CS1-B9-14-610-412-BG的Datasheet PDF文件第5页浏览型号CS1-B9-14-610-412-BG的Datasheet PDF文件第6页浏览型号CS1-B9-14-610-412-BG的Datasheet PDF文件第7页浏览型号CS1-B9-14-610-412-BG的Datasheet PDF文件第8页浏览型号CS1-B9-14-610-412-BG的Datasheet PDF文件第9页  
|
4
C-Series Circuit Breaker – General Specifications  
Electrical Tables  
Table B: Lists UL Recognized and CSA Accepted configurations and performance capabilities as a Manual Motor Controller.  
Notes:  
C-SERIES TABLE B: Manual Motor Controllers  
1. Requires branch circuit backup with a UL Listed  
Type K5 or RK5 fuse rated 15A Minimum and no  
Voltage  
Frequency  
50 / 60  
Current Rating  
Full Load Amps  
0.02 - 50  
Horsepower Ratings  
Circuit  
Configuration  
more than 4 times full load amps not to exceed  
125A for 50 Amp or less rating and not to exceed  
175A for 51 through 100A rating.  
Max. Rating  
120 1  
Phase  
Max. HP  
1
1
3
1
3
7 ꢀ  
3
5
3
5
2. UL Recognized and CSA Certified at 480V refers  
to 3 and 4 pole versions used in a 3Ø, WYE  
connected circuit or a 2 pole version with 2 poles  
breaking 1Ø and backed up with a series fusing as  
stated in note 1.  
Series,  
Shunt &  
Relay Switch  
Only  
0.02 - 20  
0.02 - 20  
0.02 - 20  
0.02 - 20  
250 1  
50 / 60  
277 1  
480 2  
50 / 60  
50 / 60  
*
Shunt and Relay Trip - Voltage Coil  
Construction not current coils  
Table C: Lists UL Recognized, CSA Accepted, VDE and TUV Certified configurations and performance capabilities as a  
Component Supplementary Protector.  
C-SERIES TABLE C: Component Supplementary Protectors  
Voltage  
Current Rating  
Short Circuit Capacity (Amps)  
UL / CSA VDE  
TUV  
Application  
Codes  
Circuit  
Configuration  
Full General  
(Inc)  
(Icn)  
(Inc)  
(Icn)  
Construction Notes  
Max.  
Rating  
With Without  
Backup Backup  
Frequency Phase Load Purpose  
With Without With Without  
Backup Backup Backup Backup  
Amps  
Amps 1  
UL / CSA  
Fuse  
Fuse  
Fuse  
Fuse  
Fuse  
Fuse  
---  
---  
---  
---  
0.10 - 70  
71 - 100 71 - 100  
1 - 50  
0.10 - 50  
0.10 - 70  
0.10 - 100  
0.10 - 90  
---  
---  
---  
---  
7,500  
10,000  
5,000  
---  
---  
---  
---  
5,000 5,000 1,500 TC1,2,OL1,U1  
---  
80  
DC  
Agency F, H, J or R  
Agency J or R  
2P, Agency J or R  
---  
5,000  
---  
---  
---  
---  
---  
5,000 TC1,2,OL0,U1  
5,000 TC1,2,OL1,U1  
5,000  
125  
DC  
DC  
---  
Series  
3,000 1,500 3,000 1,500  
---  
---  
3,000 1,500  
5,000 2,500  
---  
250  
1
3
3
---  
---  
5,000  
TC1,2,OL1,U1  
50 / 60  
---  
---  
Agency J or R  
5,000 5,000  
Rocker  
415  
50 / 60  
0.10 - 30  
---  
---  
5,000 2  
---  
---  
3,000 1,500 TC1,2,OL1,C1  
Handle, Agency F, H, J or R  
80  
250  
80  
DC  
50 / 60  
DC  
---  
1 & 3  
---  
7,500  
5,000 3,000  
7,500 ---  
5,000  
---  
Dual Coil  
0.10 - 30  
0.10 - 70  
1,500  
1,500 TC1,2,OL1,U1  
3,000  
---  
---  
---  
---  
---  
5,000 5,000 1,500 TC1,2,OL1,U1  
---  
250  
50 / 60  
1 & 3 0.10 - 70  
5,000 3,000 1,500 3,000 1,500 TC1,2,OL1,U1  
3,000 1,500  
Shunt  
Rocker  
415  
50 / 60  
3
0.10 - 30  
---  
5,000 2  
---  
3,000 1,500 TC1,2,OL1,C1  
Handle, Agency F, H, J or R  
5,000 2,500  
Notes:  
1.  
2.  
General Purpose ratings for UL/CSA only.  
Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse rated 15A minimum and no more than 4 times full load amps not to exceed 125A for 50 Amp or less  
rating and not to exceed 175 for 51 through 100 Amp rating.  
Table D: Lists UL Listed (489), CSA Certified (C22.2 No. 5.1-M) configuration and performance capabilities as a Molded Case  
Circuit Breaker.  
C-SERIES TABLE D: UL489 Listed Branch Circuit Breakers  
Voltage  
Current Rating Interrupting Capacity (Amps)  
Circuit  
Configuration  
Construction Notes  
Max. Rating Frequency Phase Full Load Amps  
Without Backup Fuse  
50,000 1  
10,000  
10,000  
10,000  
5,000  
5,000  
10,000  
5,000  
5,000  
10,000 1  
5,000  
10,000  
10,000  
Limited to 2 Poles Max from 71 - 100 Amps  
0.10 - 100  
80  
DC  
---  
2 Poles - Parallel Poles  
3 Poles - Parallel Poles  
101 - 150  
151 - 250  
0.10 - 100  
0.10 - 50  
0.10 - 50  
51 - 70  
1 - 3 Poles  
125  
125 / 250  
DC  
DC  
---  
---  
1 or 2 Poles (2 poles required for 250 Volts)  
Series  
1 - 3 Poles  
120  
120 / 240  
240  
50 / 60  
50 / 60  
50 / 60  
1
1
1
2 or 3 Poles (1 pole of a 3 pole unit is neutral)  
0.10 - 50  
1 Pole  
2 Poles  
0.10 - 30  
0.10 - 20  
0.10 - 20  
Notes:  
Special catalog  
1-2 Poles  
277  
120  
50 / 60  
50 / 60  
1
1
1
number required.  
Consult factory.  
---  
Dual Coil  
0.10 - 30  
10,000  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  