Capture anomalies while using time series measurement to monitor power lines  
Simultaneous time series monitoring for RMS fluctuations, voltage fluctuations, harmonics fluctuations, and flickering  
RMS fluctuation, voltage fluctuation, harmonic fluctuation, and flicker (IEC and ∆V10) time series data is  
displayed on the TIME PLOT screen. In addition to cursor measurement, you can enlarge events that occur in  
the voltage fluctuation event screen if a voltage dip, swell, or instantaneous interruption event occurs during  
the measurement period.  
Simply set the interval and start time series measurement to display events in the fluctuation graph  
Time series fluctuation results are displayed in the TIME PLOT screen  
Continuous data calculation processing of all data without fail!  
All measurement results are automatically recorded  
Calculation method for measured data  
-1. RMS fluctuation (dual screen display selection)  
-2. Voltage fluctuation (interval and event displays)  
-3. Harmonic fluctuation (harmonics and inter-harmonics displays)  
-4. Flicker (graph and list displays)  
-
1. RMS fluctuations/Harmonic fluctuations : Values are calculated continuously  
every 200 ms. The maximum, minimum, and average values are those applicable within the  
specified interval.  
-2. Voltage fluctuations : Values are calculated for a single waveform shifted by a half wave.  
The maximum and minimum values are those applicable within the specified interval. Detailed  
measurement of voltage fluctuations is possible because values are calculated every half wave.  
-3. Flicker : Values are calculated in accordance using calculation methods defined in the  
IEC and ∆V10 standards.  
• Pst and Plt measurement conditions according to IEC standards  
ΔV10 measurement (according to Japanese domestic guidelines)  
I
n addition to displaying the various measurements in fluctuation graphs, the 3196 also displays the maximum,  
minimum, and average values for each specified interval.  
Further, when the 3196 captures a power anomaly, an event marker appears in the upper part of the graph.  
RMS fluctuation display  
Harmonic fluctuation display  
When a power anomaly occurs during measurement, the event is indicated  
You can specify display of up to six harmonic orders.  
using the marker.  
All RMS  
measurement  
items can be  
selected for  
display.  
Dual screen  
display is  
possible for  
combinations  
such as  
Cursor values are  
displayed for the  
specified orders.  
voltage and  
current.  
Cursor values (maximum, minimum, and average values for the specified  
interval) are displayed.  
Voltage fluctuation display  
Flicker display  
Cursor values (maximum and minimum values for the specified interval) are  
displayed.  
IEC flicker display  
Displays the Pst and Plt values as a graph once every ten minutes.  
Even when a long  
interval is set,  
The Pst and Plt cursor  
values are displayed.  
momentary voltage  
fluctuations are  
accurately captured.  
Markers are displayed in blue. (  
Displays a list of detailed data for Pst and  
Plt values once every ten minutes.  
marker)  
Event display  
When an event such as a  
dip, swell, or instantaneous  
interruption occurs, the time axis  
is enlarged on the event screen.