4
Real-time data display for power supplies  
Display waveform, vector, DMM, and harmonic data in real-time  
The VIEW screen displays voltage/current waveforms, vector diagrams, DMM values (voltage, current, and  
power), and harmonic data. All data can be measured and processed simultaneously, and power conditions  
such as distortion factor, K factor, and the unbalance factor for three-phase lines can be monitored using the  
various data displays.  
Connect the 3196 to a power source to display power line data in real-time  
All power line conditions can be monitored from the VIEW screen!  
Display data in real-time  
Power management through a rich array of information  
-1. Check the distortion of power waveforms using electronic devices and electrical overloads.  
-1. Waveform display (voltage/current display, 4-channel voltage  
display, 4-channel current display)  
-2. Vector display  
-3. DMM display (power, voltage, and current displays)  
-4. Harmonics (graph and list displays)  
-2. Manage the phase of power lines. Check the phase and wiring of the VT (PT) and CT  
terminals.  
-3. Manage, maintain and check the unbalance factor, peak values, and distortion factor of  
power lines.  
-4. Assess and develop countermeasures to prevent the occurrence of harmonic power flow.  
Check for proper instrument connection using the numerical value or vector display  
Connect the 3196 to the power line to be  
monitored while viewing the connection  
diagram.Upon connection, you can confirm  
voltage, current, and power values. Further,  
through the vector display, you can verify  
proper connection of clamp-on current  
View the phases  
sensors to the VT (PT) and CT terminals.  
Waveform display  
DMM display  
This displays the voltage and current waveforms for each phase.  
Waveform display makes it easy to understand distortion conditions  
that (as with harmonics) are difficult to grasp from numerical values  
alone.  
This displays detailed data for voltage, current, and power.  
View the data necessary for power management or maintenance and  
inspection of power lines at a single glance.  
Select a waveform display  
range of 2, 4, 10, or 12  
cycles.  
Display either dual screens  
for voltage and current, or  
waveforms for individual  
voltage and current phases.  
Detailed values for  
voltage, current and  
power are displayed.  
The cursor value is displayed.  
Vector display  
Harmonics display  
This displays the voltage and current vectors for each phase, as well as  
RMS values and phase angles as numerical values.  
This displays harmonics and inter-harmonics data in a graph or list.  
You can also display the phase difference for each harmonic order, and  
Easily check the phase of three-phase lines and harmonics.  
work out the current direction for harmonics.  
You can select all of the  
connected channels.  
The harmonic  
order cursor  
value is  
Displays the unbalance  
factor when measuring  
three-phase power lines.  
(For 3P3W3M and 3P4W  
settings)  
displayed.  
Display the fundamental voltage waveform for the 1st order (U1, U2, and U3) as  
a phase angle of 360˚ as a standard.  
Ideal for checking three-phase power lines.  
Inter-harmonics display  
(light blue)  
Detailed numerical data for up to the 50th harmonic  
order is displayed in a list.