C9820
Direct Rambus Clock Generator
Preliminary
State Transitions
The clock source has three fundamental operating states. Figure 5 shows the state diagram with each transition labeled
A through J. Note that the clock source output need NOT be glitch-free during state transitions.
Vdd turn-on
G
J
Normal
F
B
A
E
D
C
Vdd turn-on
Vdd turn-on
H
Powerdown
Clk Stop
Figure 5: Clock Source State Diagram
Upon powering up the device, the device can enter any state, depending on the settings of the control signals PwrDnB
and StopB.
In Powerdown mode, the clock source is powered down with the control signal, PwrDnB, equal to 0. The control signals
S0, S1, and S2 must be stable before power is applied to the device, and can only be changed in Powerdown mode
(PwrDnB=0). The reference inputs, VddI,R and VddI,Pd, may remain on or may be grounded during the Powerdown
mode.
The control signals Mult0, Mult1 can be used in two ways. If they are changed during Powerdown mode, then the
Powerdown transistion timings determine the settling time of the DRCG. However, the Mult0 and Mult1 control signals
can also be changed during Normal mode. When the Mult control signals are “hot swapped” in this manner, the Mult
transition timings determine the settling time of the DRCG.
In Clk Stop mode, the clock source is on, but the output is disabled (StopB de-asserted). The VddI,PD reference input
may remain on or may be grounded during the Clk Stop mode. The VddI,R reference input must remain on during the
Clk Stop mode.
INTERNATIONAL MICROCIRCUITS, INC. 525 LOS COCHES ST.
MILPITAS, CA 95035. TEL: 408-263-6300. FAX 408-263-6571
http://www.imicorp.com
Rev.1.3
9/7/1999
Page 8 of 17