SERIES
GENERAL PURPOSE 4 POLE 10 AMP PLUG-IN RELAY
284
UL Recognized
File No. E13224
CONTACT RATINGS
240VAC
LOAD
120VAC
30VDC
10A
Resistive Motor
Load 80% pF.
10A
1/3Hp
10A
1/2Hp
Maximum total load for 4 pole relay is 30 Amps @
120VAC, 20Amps @ 240VAC
GENERAL SPECIFICATIONS
COIL
Pull-in Voltage:
AC: 85%, DC: 75% of nominal voltage
measured at 25˚C
10% of nominal voltage or more @ 25˚C
110% of nominal voltage
±10% Measured @ 25˚C
Dropout Voltage:
Max. allowed voltage:
Coil Resistance:
CONTACTS
Silver Cadmium Oxide.
Contact Material:
TIMING
Operate Time:
Release Time:
15 mS Max. @ Nominal Voltage.
10 mS Max. @ Nominal Voltage.
DIELECTRIC STRENGTH
All Mutually Insulated Points:
500 V rms across open contacts
1500 V rms between current carrying
parts
1000 Megohms.min. @ 500 VDC
Insulation Resistance:
TEMPERATURE
Temperature Rating:
AC: -45˚C to +50˚C @ Rated Operation.
(+65˚C for open style)
DC: -45˚C to +70 ˚C
+85˚C for open style)
LIFE EXPECTANCY
Mechanical:
10 Million Operations no load
100,000 Operations @ Rated Load.
Electrical:
MISCELLANEOUS
Enclosure:
Clear polycarbonate
5.0 oz. approx..
Weight:
COIL SPECIFICATIONS @ 25˚C
Current (MA)
Nominal
Voltage
Resistance
Resistance
Power
Consumption
Ohms ± 10% Ohms ± 10%
AC
3
12
48
-
DC
30
120
480
1920
8200
AC
560
230
115
-
DC
AC
DC
6
12
24
200 3.4VA 1.2W
100 3.4VA 1.2W
3.4VA 1.2W
3.4VA 1.2W
13-15 3.4VA 1.2W
50
25
48
120AC or
115-125DC
240AC*
870
31
4700
-*
12
-* 3.4VA 1.2W
NOTE: * For 220-250VDC coils use a 8,200 Ω, 5 Watt resistor in series with
110-125 VDC relays
WEBSITE: www.magnecraft.com - EMAIL:info@magnecraft.com - FAX ON DEMAND 1-800/891-2957 - DOCUMENT 100