 浏览型号DCM420P280M500A40的Datasheet PDF文件第15页浏览型号DCM420P280M500A40的Datasheet PDF文件第16页浏览型号DCM420P280M500A40的Datasheet PDF文件第17页浏览型号DCM420P280M500A40的Datasheet PDF文件第18页浏览型号DCM420P280M500A40的Datasheet PDF文件第20页浏览型号DCM420P280M500A40的Datasheet PDF文件第21页浏览型号DCM420P280M500A40的Datasheet PDF文件第22页浏览型号DCM420P280M500A40的Datasheet PDF文件第23页  
DCM300P280x500A40  
Output Current Limit  
n Maximum voltage rating (usually greater than the maximum  
The DCM features a fully operational current limit which effectively  
keeps the module operating inside the Safe Operating Area (SOA) for  
all valid trim and load profiles. The current limit approximates a  
“brick wall” limit, where the output current is prevented from  
exceeding the current limit threshold by reducing the output voltage  
via the internal error amplifier reference. The current limit threshold  
at nominal trim and below is typically 120% of rated output current,  
but it can vary between 100% to 130%. In order to preserve the SOA,  
when the converter is trimmed above the nominal output voltage,  
the current limit threshold is automatically reduced to limit the  
available output power.  
possible input voltage)  
n Ambient temperature  
n Breaking capacity per application requirements  
n Nominal melting I2t  
n Recommended fuse: See Agency Approvals for Recommended Fuse  
http://www.vicorpower.com/dc-dc-converter-board-mount/dcm-  
dc-dc_converter#Documentation  
Fault Handling  
Input Undervoltage Fault Protection (UVLO)  
When the output current exceeds the current limit threshold, current  
limit action is held off by 1ms, which permits the DCM to  
momentarily deliver higher peak output currents to the load. Peak  
output power during this time is still constrained by the internal  
Power Limit of the module. The fast Power Limit and relatively slow  
Current Limit work together to keep the module inside the SOA.  
Delaying entry into current limit also permits the DCM to minimize  
droop voltage for load steps.  
The converter’s input voltage is monitored to detect an input under  
voltage condition. If the converter is not already running, then it will  
ignore enable commands until the input voltage is greater than  
VIN-UVLO+. If the converter is running and the input voltage falls  
below VIN-UVLO-, the converter recognizes a fault condition, the  
powertrain stops switching, and the output voltage of the unit falls.  
Input voltage transients which fall below UVLO for less than tUVLO  
may not be detected by the fault proection logic, in which case the  
converter will continue regular operation. No protection is required  
in this case.  
Sustained operation in current limit is permitted, and no derating of  
output power is required, even in an array configuration.  
Some applications may benefit from well matched current  
distribution, in which case fine tuning sharing via the trim pins  
permits control over sharing. The DCM does not require this for  
proper operation, due to the power limit and current limit behaviors  
described here.  
Once the UVLO fault is detected by the fault protection logic, the  
converter shuts down and waits for the input voltage to rise above  
VIN-UVLO+. Provided the converter is still enabled, it will then restart.  
Input Overvoltage Fault Protection (OVLO)  
The converter’s input voltage is monitored to detect an input over  
voltage condition. When the input voltage is more than the  
Current limit can reduce the output voltage to as little as the UVP  
threshold (VOUT-UVP). Below this minimum output voltage  
compliance level, further loading will cause the module to shut  
down due to the output undervoltage fault protection.  
VIN-OVLO+, a fault is detected, the powertrain stops switching, and the  
output voltage of the converter falls.  
After an OVLO fault occurs, the converter will wait for the input  
voltage to fall below VIN-OVLO-. Provided the converter is still enabled,  
the powertrain will restart.  
Line Impedance, Input Slew rate and Input Stability Requirements  
Connect a high-quality, low-noise power supply to the +IN and –IN  
terminals. Additional capacitance may have to be added between +IN  
and –IN to make up for impedances in the interconnect cables as  
well as deficiencies in the source.  
The powertrain controller itself also monitors the input voltage.  
Transient OVLO events which have not yet been detected by the fault  
sequence logic may first be detected by the controller if the input  
slew rate is sufficiently large. In this case, powertrain switching will  
immediately stop. If the input voltage falls back in range before the  
fault sequence logic detects the out of range condition, the  
powertrain will resume switching and the fault logic will not  
interrupt operation Regardless of whether the powertrain is running  
at the time or not, if the input voltage does not recover from OVLO  
before tOVLO, the converter fault logic will detect the fault.  
Excessive source impedance can bring about system stability issues  
for a regulated DC-DC converter, and must either be avoided or  
compensated by filtering components. A 100 µF input capacitor is  
the minimum recommended in case the source impedance is  
insufficient to satisfy stability requirements.  
Additional information can be found in the filter design application  
note:  
www.vicorpower.com/documents/application_notes/vichip_appnote23.pdf  
Output Undervoltage Fault Protection (UVP)  
Please refer to this input filter design tool to ensure input stability:  
http://app2.vicorpower.com/filterDesign/intiFilter.do.  
The converter determines that an output overload or short circuit  
condition exists by measuring its primary sensed output voltage and  
the output of the internal error amplifier. In general, whenever the  
powertrain is switching and the primary-sensed output voltage falls  
below VOUT-UVP threshold, a short circuit fault will be registered. Once  
an output undervoltage condition is detected, the powertrain  
immediately stops switching, and the output voltage of the converter  
falls. The converter remains disabled for a time tFAULT. Once recovered  
and provided the converter is still enabled, the powertrain will again  
Ensure that the input voltage slew rate is less than 1V/us, otherwise a  
pre-charge circuit is required for the DCM input to control the input  
voltage slew rate and prevent overstress to input stage components.  
Input Fuse Selection  
The DCM is not internally fused in order to provide flexibility in  
configuring power systems. Input line fusing is recommended at the  
system level, in order to provide thermal protection in case of  
catastrophic failure. The fuse shall be selected by closely matching  
system requirements with the following characteristics:  
enter the soft start sequence after tINIT and tON  
.
Temperature Fault Protections (OTP)  
The fault logic monitors the internal temperature of the converter. If  
the measured temperature exceeds TINT-OTP, a temperature fault is  
registered. As with the under voltage fault protection, once a  
n Current rating (usually greater than the DCM converter’s  
maximum current)  
DCMDC-DC Converter  
Rev 1.1  
vicorpower.com  
800 927.9474  
Page 19 of 25  
10/2015  