 浏览型号DCM420P280M500A40的Datasheet PDF文件第14页浏览型号DCM420P280M500A40的Datasheet PDF文件第15页浏览型号DCM420P280M500A40的Datasheet PDF文件第16页浏览型号DCM420P280M500A40的Datasheet PDF文件第17页浏览型号DCM420P280M500A40的Datasheet PDF文件第19页浏览型号DCM420P280M500A40的Datasheet PDF文件第20页浏览型号DCM420P280M500A40的Datasheet PDF文件第21页浏览型号DCM420P280M500A40的Datasheet PDF文件第22页  
DCM300P280x500A40  
Nominal Output Voltage Temperature Coefficient  
Design Guidelines  
Building Blocks and System Design  
The DCM™ converter input accepts the full 200 to 420 V range, and it  
generates an isolated trimmable 28.0 Vdc output. Multiple DCMs  
may be paralleled for higher power capacity via wireless load  
sharing, even when they are operating off of different input voltage  
supplies.  
A second additive term to the programmed output voltage is based  
on the temperature of the module. This term permits improved  
thermal balancing among modules in an array, especially when the  
factory nominal trim point is utilized (trim mode inactive). This term  
is much smaller than the load line described above, representing  
only a -3.73 mV/°C change. Regulation coefficient is relative to 25°C.  
For nominal trim and full load, the output voltage relates to the  
temperature according to the following equation:  
The DCM converter provides a regulated output voltage around  
defined nominal load line and temperature coefficients. The load line  
and temperature coefficients enable configuration of an array of  
DCM converters which manage the output load with no share bus  
among modules. Downstream regulators may be used to provide  
tighter voltage regulation, if required.  
VOUT-FL = 28.0 -3.733 • 0.001 • (TINT - 25)  
(2)  
where TINT is in °C.  
The DCM300P280x500A40 may be used in standalone applications  
where the output power requirements are up to 500 W. However, it is  
easily deployed as arrays of modules to increase power handling  
capacity. Arrays of up to eight units have been qualified for 4000 W  
capacity. Application of DCM converters in an array requires no  
derating of the maximum available power versus what is specified  
for a single module.  
The impact of temperature coefficient on the output voltage is  
absolute, and does not scale with trim or load.  
Trim Mode and Output Trim Control  
When the input voltage is initially applied to a DCM, and after tINIT  
elapses, the trim pin voltage VTR is sampled. The TR pin has an  
internal pull up resistor to VCC, so unless external circuitry pulls the  
pin voltage lower, it will pull up to VCC. If the initially sampled trim  
pin voltage is higher than VTRIM-DIS, then the DCM will disable  
trimming as long as the VIN remains applied. In this case, for all  
subsequent operation the output voltage will be programmed to the  
nominal. This minimizes the support components required for  
applications that only require the nominal rated Vout, and also  
provides the best output setpoint accuracy, as there are no additional  
errors from external trim components  
Soft Start  
When the DCM starts, it will go through a soft start. The soft start  
routine ramps the output voltage by modulating the internal error  
amplifier reference. This causes the output voltage to approximate a  
piecewise linear ramp. The output ramp finishes when the voltage  
reaches either the nominal output voltage, or the trimmed output  
voltage in cases where trim mode is active.  
During soft-start, the maximum load current capability is reduced.  
Until Vout achieves at least VOUT-FL-THRESH, the output current must be  
less than IOUT-START in order to guarantee startup. Note that this is  
current available to the load, above that which is required to charge  
the output capacitor.  
If at initial application of VIN, the TR pin voltage is prevented from  
exceeding VTRIM-EN, then the DCM will activate trim mode, and it will  
remain active for as long as VIN is applied.  
VOUT set point under full load and room temperature can be  
calculated using the equation below:  
Nominal Output Voltage Load Line  
VOUT-FL @ 25°C = 11.64 + (21.910 • VTR/VCC  
)
(3)  
Throughout this document, the programmed output voltage, (either  
the specified nominal output voltage if trim is inactive or the  
trimmed output voltage if trim is active), is specified at full load, and  
at room temperature. The actual output voltage of the DCM is given  
by the programmed trimmed output voltage, with modification  
based on load and temperature. The nominal output voltage is 28.0  
V, and the actual output voltage will match this at full load and room  
temperature with trim inactive.  
Note that the trim mode is not changed when a DCM recovers from  
any fault condition or being disabled.  
Module performance is guaranteed through output voltage trim  
range VOUT-TRIMMING. If VOUT is trimmed above this range, then certain  
combinations of line and load transient conditions may trigger the  
output OVP.  
The largest modification to the actual output voltage compared to  
the programmed output is due to the 5.263% VOUT-NOM load line,  
which for this model corresponds to ΔVOUT-LOAD of 1.4736V. As the  
load is reduced, the internal error amplifier reference, and by  
extension the output voltage, rises in response. This load line is the  
primary enabler of the wireless current sharing amongst an array of  
DCMs.  
Overall Output Voltage Transfer Function  
Taking load line (equation 1), temperature coefficient (equation 2)  
and trim (equation 3) into account, the general equation relating the  
DC VOUT to programmed trim (when active), load, and temperature is  
given by:  
VOUT = 11.64 + (21.910 • VTR/VCC  
)
The load line impact on the output voltage is absolute, and does not  
scale with programmed trim voltage.  
+ 1.4736 • (1 - IOUT / 17.86)  
-3.733 • 0.001 • (TINT -25) + VOUT-LL  
(4)  
For a given programmed output voltage, the actual output voltage  
versus load current at for nominal trim and room temperature is  
given by the following equation:  
Finally, note that when the load current is below 10% of the rated  
capacity, there is an additional ∆V which may add to the output  
voltage, depending on the line voltage which is related to Burst  
Mode. Please see the section on Burst Mode below for details.  
VOUT @ 25° = 28.0 + 1.4736 • (1 - IOUT / 17.86)  
(1)  
Use 0 V for ∆VOUT-LL when load is above 10% of rated load. See  
section on Burst Mode operation for light load effects on output  
voltage.  
DCMDC-DC Converter  
Rev 1.1  
vicorpower.com  
800 927.9474  
Page 18 of 25  
10/2015  