 浏览型号BCM352F125M300A00的Datasheet PDF文件第13页浏览型号BCM352F125M300A00的Datasheet PDF文件第14页浏览型号BCM352F125M300A00的Datasheet PDF文件第15页浏览型号BCM352F125M300A00的Datasheet PDF文件第16页浏览型号BCM352F125M300A00的Datasheet PDF文件第18页浏览型号BCM352F125M300A00的Datasheet PDF文件第19页浏览型号BCM352F125M300A00的Datasheet PDF文件第20页浏览型号BCM352F125M300A00的Datasheet PDF文件第21页  
BCM352x125y300A00  
Current Sharing  
Fuse Selection  
The performance of the SACtopology is based on efficient  
transfer of energy through a transformer without the need of  
closed loop control. For this reason, the transfer characteristic  
can be approximated by an ideal transformer with a positive  
temperature coefficient series resistance.  
In order to provide flexibility in configuring power systems  
VI Chip® modules are not internally fused. Input line fusing  
of VI Chip products is recommended at system level to provide  
thermal protection in case of catastrophic failure.  
The fuse shall be selected by closely matching system  
requirements with the following characteristics:  
This type of characteristic is close to the impedance characteristic  
of a DC power distribution system both in dynamic (AC) behavior  
and for steady state (DC) operation.  
n Current rating (usually greater than maximum current  
of BCM module)  
When multiple BCM modules of a given part number are  
connected in an array they will inherently share the load current  
according to the equivalent impedance divider that the system  
implements from the power source to the point of load.  
n Maximum voltage rating (usually greater than the maximum  
possible input voltage)  
n Ambient temperature  
n Nominal melting I2t  
Some general recommendations to achieve matched array  
impedances include:  
n Recommend fuse: 2.5A Bussmann PC–Tron Fuse or 3.15A  
SOC type 36CFA Fuse.  
n Dedicate common copper planes within the PCB  
to deliver and return the current to the modules.  
Reverse Operation  
n Provide as symmetric a PCB layout as possible among modules  
n Apply same input / output filters (if present) to each unit.  
BCM modules are capable of reverse power operation. Once the  
unit is started, energy will be transferred from secondary back to  
the primary whenever the secondary voltage exceeds VIN • K. The  
module will continue operation in this fashion for as long as no  
faults occur.  
For further details see AN:016 Using BCM Bus Converters  
in High Power Arrays.  
The BCM352x125y300A00 has not been qualified for continuous  
operation in a reverse power condition. Furthermore fault  
protections which help protect the module in forward operation  
will not fully protect the module in reverse operation.  
ZIN_EQ1  
ZOUT_EQ1  
BCM®1  
R0_1  
VIN  
VOUT  
Transient operation in reverse is expected in cases where there is  
significant energy storage on the output and transient voltages  
appear on the input. Transient reverse power operation of less than  
10ms, 10% duty cycle is permitted and has been qualified to cover  
these cases.  
ZOUT_EQ2  
ZIN_EQ2  
BCM®2  
R0_2  
+
Load  
DC  
ZOUT_EQn  
BCM®n  
R0_n  
ZIN_EQn  
Figure 21 — BCM module array  
BCM® Bus Converter  
Page 17 of 21  
Rev 2.0  
08/2016  
vicorpower.com  