RPM-Based Fan Controller with HW Thermal Shutdown  
Datasheet  
6.30  
TACH Target Register  
Table 6.46 TACH Target Register  
ADDR  
R/W  
REGISTER  
B7  
B6  
B5  
B4  
B3  
B2  
B1  
B0  
DEFAULT  
Fan TACH  
Target Low  
Byte  
4Ch  
4Dh  
R/W  
R/W  
16  
8
4
2
1
-
-
-
F8h  
FFh  
TACH Target  
4096 2048 1024  
512  
256  
128  
64  
32  
The TACH Target Register holds the target tachometer value that is maintained by the RPM based  
Fan Speed Control Algorithm.  
The value in the TACH Target Register will always reflect the current TACH Target value. If the Look  
Up Table is active and configured to operate in RPM Mode, then this register will be read only. Writing  
to this register will have no affect and the data will not be stored.  
If the algorithm is enabled then setting the TACH Target Register to FFh will disable the fan driver (set  
the PWM duty cycle to 0%). Setting the TACH Target to any other value (from a setting of FFh) will  
cause the algorithm to invoke the Spin Up Routine after which it will function normally.  
6.31  
TACH Reading Register  
Table 6.47 TACH Reading Register  
ADDR  
R/W  
REGISTER  
B7  
4096 2048 1024  
16  
B6  
B5  
B4  
B3  
B2  
B1  
B0  
DEFAULT  
4Eh  
R
Fan TACH  
512  
256  
128  
64  
32  
FFh  
Fan TACH  
Low Byte  
4Fh  
R
8
4
2
1
-
-
-
F8h  
The TACH Reading Register contents describe the current tachometer reading for the fan. By default,  
the data represents the fan speed as the number of 32kHz clock periods that occur for a single  
revolution of the fan.  
Equation [3] shows the detailed conversion from TACH measurement (COUNT) to RPM while Equation  
[4] shows the simplified translation of TACH Reading Register count to RPM assuming a 2-pole fan,  
measuring 5 edges, with a frequency of 32.768kHz.  
See Appendix B for a table enumerating the RPM to TACH conversion for the default settings.  