RPM-Based Fan Controller with HW Thermal Shutdown
Datasheet
Table 6.41 Spin Time
SPINUP_TIME[1:0]
1
0
TOTAL SPIN UP TIME
0
0
1
1
0
1
0
1
250 ms
500 ms (default)
1 sec
2 sec
The Fan Spin Up Configuration Register is software locked.
6.26
Fan Step Register
Table 6.42 Fan Step Register
ADDR
R/W
REGISTER
B7
B6
B5
B4
B3
B2
B1
B0
DEFAULT
47h
R/W
Fan Max Step
-
-
32
16
8
4
2
1
10h
The Fan Step Register, along with the Update Time, control the ramp rate of the fan driver response.
The value of the registers represents the maximum step size each fan driver will take between update
times (see Section 6.22).
All modes of operation have the options to use the Fan Step Register (and update times) for ramp rate
control based on the Fan Configuration 2 Register settings. The Fan Speed Control Algorithm will
always use the Fan Step Register settings (but see application note below).
APPLICATION NOTE: If the Fan Speed Control Algorithm is used, the default settings in the Fan Configuration 2
Register will cause the maximum fan step settings to be ignored.
The Fan Step Register is software locked.
6.27
Fan Minimum Drive Register
Table 6.43 Minimum Fan Drive Register
ADDR
R/W
REGISTER
B7
B6
B5
B4
B3
B2
B1
B0
DEFAULT
Fan Minimum
Drive
66h
(40%)
48h
R/W
128
64
32
16
8
4
2
1
The Fan Minimum Drive Register stores the minimum drive setting for the RPM based Fan Speed
Control Algorithm. This register is not used if the FSC is not active. The RPM based Fan Speed Control
Algorithm will not drive the fan at a level lower than the minimum drive unless the target TACH Target
is set at FFh (see Section 6.30)
During normal operation, if the fan stops for any reason (including low drive), the RPM based Fan
Speed Control Algorithm will attempt to restart the fan. Setting the Fan Minimum Drive Registers to a
Revision 0.85 (01-29-08)
SMSC EMC2103
DATA6S0HEET