欢迎访问ic37.com |
会员登录 免费注册
发布采购

1489-A1D130R 参数 Datasheet PDF下载

1489-A1D130R图片预览
型号: 1489-A1D130R
PDF下载: 下载PDF文件 查看货源
内容描述: [Thermal Magnetic Circuit Breaker]
分类和应用:
文件页数/大小: 22 页 / 441 K
品牌: ROCKWELL [ ROCKWELL INTERNATIONAL CORPORATION. ]
 浏览型号1489-A1D130R的Datasheet PDF文件第12页浏览型号1489-A1D130R的Datasheet PDF文件第13页浏览型号1489-A1D130R的Datasheet PDF文件第14页浏览型号1489-A1D130R的Datasheet PDF文件第15页浏览型号1489-A1D130R的Datasheet PDF文件第17页浏览型号1489-A1D130R的Datasheet PDF文件第18页浏览型号1489-A1D130R的Datasheet PDF文件第19页浏览型号1489-A1D130R的Datasheet PDF文件第20页  
Bulletin 1489-A  
Circuit Breaker  
Product Description  
HACR Rating  
Bulletin 1489-A Ambient Temperature Derating  
The standard tripping characteristic for Bulletin 1489-A is Type C.  
Type C has a magnetic trip activated at 5…10 times the rated  
current of the circuit breaker. The reference temperature for the  
thermal tripping characteristics is 40 °C. The Type C characteristic  
will suit most applications.  
Bulletin 1489-A Circuit Breakers are rated as Heating, Air  
Conditioning and Refrigeration circuit breakers as defined by UL  
489, paragraph 6.7 and may used in this type of application.  
0
SWD Rating  
The Bulletin 1489 breakers (0.5 … 20 A) are rated as SWD and as  
such may be applied to switch fluorescent lighting loads up to their  
current and voltage maximum.  
In rare occurrences when the Type C characteristic does not fully  
meet the application, the following additional magnetic trip  
characteristic is available:  
1
Current Limiting  
Type D allows for transients approximately twice as high as the  
standard Type C.  
Bulletin 1489-A Circuit Breakers are rated as current limiting circuit  
breakers as defined by UL 489, paragraph 8.6.  
Use the following table and graph to determine the current rating for  
the breaker if the ambient is significantly different than 40 °C.  
2
The Bulletin 1489-A line features the ability to achieve short circuit  
interruptions far more effectively than conventional breakers. In  
conventional circuit breakers, the short circuit interruption time  
required is approximately one or two half cycles of an AC sine wave.  
When the contacts open, the resulting arc continues to burn until  
the current level passes through zero. The arc may re-ignite  
because of the insufficient width of the contact gap. The current  
that flows until the arc is extinguished produces a heating effect  
proportional to the I2t value (let-through-energy) of the fault current.  
Bulletin 1489-A Ambient Temperature Derating  
Calibration Temperature 40º C (UL)  
Application below 0º C is for non-condensing  
atmosphere  
3
Ambient Temperature (°C)  
The Bulletin 1489-A device is designed to substantially reduce the  
amount of let-through-current and the resulting let-through-energy  
that can damage protected components. The Bulletin 1489 has the  
ability to interrupt short circuit current within the first half cycle of  
the fault. Limiting let-through current and energy will protect against  
the harmful effects of overcurrent and is focused primarily on  
avoiding the following:  
4
5
Excessive Heat  
Mechanical Damage  
-25 -20 -10  
0
10  
20  
30  
35  
40  
45  
50  
55  
Both of these factors are proportional to the square of the current.  
Thermal energy is proportional to the square of the RMS value and  
magnetic forces are proportional to the square of the peak value.  
The most effective way to provide protection is to substantially limit  
let-through-energy. This provides the following advantages  
0.5 0.6 0.6 0.6 0.6 0.6 0.5 0.5 0.5 0.50 0.5 0.5 0.5  
1.0 1.3 1.2 1.2 1.2 1.1 1.1 1.0 1.0 1.0 1.0 1.0 0.9  
1.5 1.9 1.9 1.8 1.7 1.7 1.6 1.6 1.5 1.5 1.5 1.4 1.4  
2.0 2.5 2.5 2.4 2.3 2.2 2.2 2.1 2.0 2.0 2.0 1.9 1.9  
3.0 3.8 3.7 3.6 3.5 3.4 3.2 3.1 3.1 3.0 2.9 2.9 2.8  
4.0 5.0 5.0 4.8 4.6 4.5 4.3 4.2 4.1 4.0 3.9 3.8 3.8  
5.0 6.3 6.2 6.0 5.8 5.6 5.4 5.2 5.1 5.0 4.9 4.8 4.7  
6.0 7.5 7.4 7.2 7.0 6.7 6.5 6.2 6.1 6.0 5.9 5.8 5.6  
7.0 8.8 8.7 8.4 8.1 7.8 7.6 7.3 7.1 7.0 6.9 6.7 6.6  
8.0 10.0 9.9 9.6 9.3 9.0 8.6 8.3 8.2 8.0 7.8 7.7 7.5  
10.0 12.6 12.4 12.0 11.6 11.2 10.8 10.4 10.2 10 9.8 9.6 9.4  
13.0 16.3 16.1 15.6 15.1 14.6 14.0 13.5 13.3 13 12.7 12.5 12.2  
15.0 18.8 18.6 18.0 17.4 16.8 16.2 15.6 15.3 15 14.7 14.4 14.1  
16.0 20.1 19.8 19.2 18.6 17.9 17.3 16.6 16.3 16 15.7 15.4 15.0  
20.0 25.1 24.8 24.0 23.2 22.4 21.6 20.8 20.4 20 19.6 19.2 18.8  
25.0 31.4 31.0 30.0 29.0 28.0 27.0 26.0 25.5 25 24.5 24.0 23.5  
30.0 37.7 37.2 36.0 34.8 33.6 32.4 31.2 30.6 30 29.4 28.8 28.2  
32.0 40.2 39.7 38.4 37.1 35.8 34.6 33.3 32.6 32 31.4 30.7 30.1  
40.0 43.9 43.4 42.0 40.6 39.2 37.8 36.4 35.7 35 34.3 33.6 32.9  
6
Far less damage at the location of the short circuit.  
7
Fast electric separation of a faulty unit from the system, especially  
power supplies connected in parallel that are switched off when  
the voltage of the power bus drops below a certain level.  
Far less wear on the miniature circuit breaker itself. This means  
more safe interruptions.  
8
Better protection of all components in the short circuit path.  
Far wider range of selective action when used with an upstream  
protective device. (No nuisance shut downs from feeder line  
interruptions, causing a blackout in all connected branches.)  
9
The following values are applicable to the whole product range with  
frequency of 50/60 Hz.  
The values were derived from worst case V AC testing of:  
D trip 40 A, 240V AC @ 10 kA  
10  
11  
12  
13  
Care should be taken for application below 0 °C. These devices are not  
certified to operate correctly in the presence of ice.  
All other specifications for standard Bulletin 1489-A products remain  
unchanged.  
The ambient temperature derating applies to applications of the device as an  
IEC Miniature Circuit Breaker (MCB), following 60 947-2 and as Circuit  
Breaker to UL489/CSA 22.2 No 5..  
Ambient temperature refers to the free air temperature in contact with the  
1489 device  
D trip 32 A, 480Y/277V AC @ 10 kA  
D trip 20 A, 480Y/277V AC @ 14 kA  
Current-Limiting at 240V / 10 kA1p, 2p, 3p I2t = 43 kA²s and I  
peak = 6.2 kA  
Current-Limiting at 480Y/277V / 10 kA 1p, 2p, 3p I2t = 60 kA²s and  
I peak = 6.2 kA  
Current-Limiting at 480Y/277V / 14 kA 1p, 2p, 3p I2t = 65 kA²s and  
I peak = 7.5 kA  
www.ab.com/catalogs  
Preferred availability cat. nos. are bold.  
7-17  
Publication A117-CA001A-EN-P  
 复制成功!