FNP1500/1800 Front-Ends
& FNR-3 Power Shelves Data Sheet
Safety Specifications
Maximum electric strength testing is performed in the factory according to EN 550116, IEC/EN 60950, and UL 60950.
Input-to-output electric strength tests should not be repeated in the field. Power-One will not honor any warranty claims resulting
from electric strength field tests.
Parameter
Agency approvals
Conditions/description
Min
Nom
Max
Unit
UL60950, (UL) CSA 60950 (cUL),
EN 60950(TÜV), CE Mark for LVD
Insulation safety rating
Input to case
Input to output
Output to case
Basic
Reinforced
Functional
Electric strength test voltage
Input to case
Input to output
Output to case
2.12
4.2 1
0.5
kVDC
kVDC
kVDC
kVDC
Output 1 to output 2
0.1
1 Subassemblies are pre-tested with 4.2 kVDC in accordance with EN50116 and IEC/EN60950.
EMC Specifications
Parameter
Description
Criterion
Electrostatic discharge
Electromagnetic field
Electrical fast transients/burst
Surge
Voltage dips and interruptions
RF conducted immunity
IEC/EN 61000-4-2, level 4
IEC/EN 61000-4-3, level 3
IEC/EN 61000-4-4, level 3
IEC/EN 61000-4-5, level 3
IEC/EN 61000-4-11
Performance criterion B
Performance criterion A
Performance criterion B
Performance criterion B
Performance criterion B or better
IEC/EN 61000-4-6
10 VAC, AM 80 %, 1 kHz
Performance criterion A
Emissions conducted
Emissions radiated
Harmonics
Voltage fluctuation and flicker
Voltage sag
CISPR 22/EN 55022/EN 61204
CISPR 22/EN 55022/EN 61204
IEC/EN 61000-3-2
IEC/EN 61000-3-3
SEMI F47-0200 (High Line 230V)
Class B
Class A
Class B
Pass
Pass
Input Specifications
Specification is valid for input voltage, load, and temperature ranges, unless otherwise stated.
Parameter
Input voltage
Conditions/description
Min
85
Nom
230
Max
264
63
Unit
VAC
Hz
Input frequency
47
50/60
Turn-on input voltage
Turn-off input voltage
Inrush current limitation
Ramping up
79
85
VAC
VAC
Ramping down
70
78
115/230 VAC acc. ETS 300 132-1
< 100 ms
50
20
Apk
ms
Hold-up time
Power factor
After last AC line peak ,Vi = 230 VAC, Po nom
Vi nom, Io nom
20
0.95
89 1
W/VA
%
Efficiency
Vi = 230 VAC, Io nom, TC = 25 °C
90
Max input current
Input connector
1 87% for FNP1500-12
Arms
16A – 20 A / 250 VAC; according to IEC320 C19
MCD10074 Rev. 1.2, 15-Apr-10
Page 3 of 17