FNP1500/1800 Front-Ends
& FNR-3 Power Shelves Data Sheet
Model Selection
Output 1
Output 2
Input voltage
Rated power
W
Compatible
Shelf 2
Model
VAC
Vo1 nom
VDC
Io1 max
ADC
Vo2 nom
VDC
Io2 max
ADC
auto selected 1
108 – 264
85 – 105
12
12
129 @ 11.64V
101.8 @ 11.78A
12
12
1
1
1512
1212
FNP1500-12G
FNP1500-48G
FNR-3-12G
FNR-3-48G
105 – 264
85 – 105
48
48
32.2
25.4
12
12
1
1
1512
1212
180 – 264
105 – 180
85 – 105
12
12
12
150 @ 11.52V
129 @ 11.64V
101.8A @ 11.78V
12
12
12
1
1
1
1740
1512
1212
FNP1800-12G
FNR-3-12G
FNR-3-48G
180 – 264
105 – 180
85 – 105
48
48
48
39.2
32.2
25.4
12
12
12
1
1
1
1812
1512
1212
FNP1800-48G
1
The available output power is automatically adjusted depending on the input voltage.
2
1U standard racks are available from Power-One. See the Rack (Power Shelf) section of this data sheet for configurations and details.
Absolute Maximum Ratings
Stress in excess of the absolute maximum ratings may cause performance degradation, adversely effect long-term reliability, or
cause permanent damage to the converter.
Parameter
Conditions/Description
Min
Max
Unit
Input voltage
Continuous
Transient, 60 ms max.
264
300
VAC
VAC
Operating ambient temperature
Vi min-Vi max, Io nom, cooling by internal fan
@ 100 % load
@ 50 % load
0
0
50
70
°C
°C
Storage temperature
Non-Operating
-40
85
°C
Environmental, Mechanical, & Reliability Specifications
Parameter
Conditions/Description
Min
Nom
Max
Unit
Altitude
Operating
Non-Operating
10 k
40 k
ASL Ft.
ASL Ft.
Relative humidity, non-condensing
Operating
Storage
10
5
90
95
% RH
% RH
%/K
Temperature coefficient
Shock
0 °C to 70 °C (after 15 min warm-up)
IEC/EN 60068-2-27, 11 ms
0.02
40
gpk
Sinusoidal vibration
IEC/EN 60068-2-6
2-8 Hz
7.5
2
4
mil
gpk
gpk
8-200 Hz
200-500 Hz
Random vibration
MTBF
10-2000 Hz
Calculated per Bellcore (SR-332, Issue 1):
GB 25 °C
6.15
grms
230
TBD
250
kh
kh
kh
GB 25 °C (FNP1500-12G)
Demonstrated
MCD10074 Rev. 1.2, 15-Apr-10
Page 2 of 17
www.power-one.com