 浏览型号3G5A2-OC221-PE的Datasheet PDF文件第88页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第89页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第90页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第91页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第93页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第94页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第95页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第96页  
Error Messages and Alarm Outputs  
Section 5-1  
Non-fatal Errors  
Item  
Cause  
CPU indicators  
Peripheral  
Device error  
Power RUN ERROR WDT ALARM OUT INT COMM  
message  
System error  
(FAL)  
Program has ex-  
ecuted FAL  
Lit  
Lit  
Unlit  
Unlit Lit  
---  
---  
SYSTEM ERR  
FAL  
JMP error  
Destination of JMP/ Lit  
CJP/CJPN is miss-  
ing.  
Lit  
Unlit  
Unlit Lit  
---  
---  
JMP ERR  
Indirect DM  
BCD error  
Data for indirectly  
addressed DM is  
not BCD.  
Lit  
Lit  
Lit  
Lit  
Unlit  
Unlit  
Unlit  
Unlit Lit  
Unlit Lit  
Unlit Lit  
---  
---  
---  
---  
---  
---  
INDIRECT DM  
BCD ERR  
Non-fatal SFC  
error  
Error has occurred Lit  
during SFC execu-  
tion.  
SFC CONTIN-  
UE  
ERR  
I/O verification  
error  
I/O table contains a Lit  
different number of  
I/O points than is  
I/O VERIFY  
ERR  
actually mounted.  
CPU Bus Unit  
error  
Parity error occurs  
during data transfer  
between CPU and  
CPU Bus Unit.  
Lit  
Lit  
Lit  
Lit  
Lit  
Lit  
Lit  
Lit  
Lit  
Lit  
Unlit  
Unlit  
Unlit  
Unlit  
Unlit  
Unlit Lit  
Unlit Lit  
Unlit Lit  
Unlit Lit  
Unlit Lit  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
CPU SPECIAL  
UNIT ERR  
SYSMAC  
BUS/2 error  
Error occurs be-  
tween Master and  
Slave in SYSMAC  
BUS/2.  
SYSMAC  
BUS/2 ERR  
SYSMAC BUS Error occurs be-  
error  
SYSMAC BUS  
ERR  
tween Master and  
Slave in SYSMAC  
BUS.  
Battery failure  
Battery of CPU or  
Memory Card is not  
connected or bat-  
tery voltage is low.  
BATTERY ERR  
CPU Bus Unit  
setting error  
Number assigned  
to CPU Bus Unit  
does not agree with  
registered unit  
number.  
CPU SPECIAL  
UNIT SETTING  
ERR  
Momentary  
Momentary power  
Lit  
Lit  
Unlit  
Unlit Lit  
---  
---  
PROTECTED  
power interrup- interruption oc-  
tion  
curred (when spe-  
cified as error by in  
PC Setup)  
Output inhibit  
(*)  
Bit A00015 is ON.  
Lit  
Lit  
Lit  
Unlit  
Unlit  
Unlit ---  
Unlit ---  
Lit  
---  
---  
Lit  
---  
---  
Host link com-  
munication  
Error has occurred Lit  
during host link  
communication  
Note *All outputs of the I/O Units are turned OFF.  