 浏览型号3G5A2-OC221-PE的Datasheet PDF文件第85页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第86页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第87页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第88页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第90页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第91页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第92页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第93页  
Error Messages and Alarm Outputs  
Section 5-1  
5-1 Error Messages and Alarm Outputs  
When an error occurs after operation has once started, an error code is set in  
Word A400. If two or more errors occur simultaneously, the error code having the  
highest priority is set. In the following table, the error having the highest priority is  
shown at the top of each column.  
The status of indicators for which status is not show does not affect the error con  
-
dition.  
Startup Errors  
Item  
Cause  
CPU indicators  
Peripheral  
Device error  
message  
Power RUN ERROR WDT ALARM OUT INT COMM  
Start input wait START input of  
CPU Rack Power  
Lit  
Unlit ---  
---  
---  
---  
---  
CPU WAITING  
Supply Unit is OFF.  
No SYSMAC  
BUS terminator set.  
Terminator is not  
Lit  
Lit  
Unlit ---  
Unlit ---  
---  
---  
---  
---  
---  
---  
---  
---  
CPU WAITING  
CPU WAITING  
CPU Bus Unit  
initialization  
Terminator of  
SYSMAC BUS/2 is  
missing, or CPU  
Bus Unit is still  
initializing.  
I/O verify error  
(PC Setup)  
I/O Unit has been  
removed.  
Lit  
Unlit ---  
---  
Lit  
---  
---  
CPU WAITING  
Startup Errors (cont’d)  
Item  
RUN  
Auxiliary Area data  
Corrective action  
output Error flags  
Error  
code  
Start input wait  
OFF  
OFF  
A30600 ON None  
Turn ON the CPU Rack Power Supply Unit START  
input, or short-circuit the START input terminals.  
No SYSMAC BUS  
terminator  
A30602 ON None  
Turn on the power to the Remote I/O Slave Unit.  
Specify the Unit connected last as the terminator or wait  
until CPU Bus Units complete initialization.  
CPU Bus Unit initialization OFF  
A30603 ON None  
Turn on the power to the Remote I/O Slave Unit.  
Specify the Unit connected last as the terminator.  
I/O verify error  
(PC Setup)  
OFF  
A30601 ON 00E7  
A40209 ON  
Verify the I/O table. Correct the table if necessary by  
create a new one.  
76  