 浏览型号3G5A2-OC221-PE的Datasheet PDF文件第87页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第88页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第89页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第90页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第92页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第93页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第94页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第95页  
Error Messages and Alarm Outputs  
Section 5-1  
Fatal Errors (cont’d)  
Item  
RUN  
Auxiliary Area data  
Error data  
Corrective action  
output Error flags  
Error  
code  
Power interruption  
OFF  
None  
A012 to A013 (Power In- None  
terruption Time)  
A014 (Number of Power  
Check the supply voltage, the  
Power Supply Unit wiring, and the  
defined power interruption time.  
Interruptions)  
Expansion CPU  
Rack power OFF  
OFF  
OFF  
OFF  
None  
None  
None  
None  
None  
80FF  
Turn on the power to the Expan-  
sion CPU Rack.  
CPU error  
Turn the power OFF and ON  
again.  
Memory error  
A40115 ON A403 (Memory Area Er- 80F1  
ror Location)  
Check/correct the program. Cor-  
rectly mount the Memory Card  
and Expansion DM Unit. Check  
the battery connection. Perform  
the error clear operation after cor-  
rective actions have been taken.  
I/O bus error  
OFF  
OFF  
OFF  
OFF  
A40114 ON AR404 (I/O Bus Error  
80C0-  
Check the cables between the  
Racks. Perform the error clear op-  
eration after corrective action has  
been taken.  
Rack and Slot Numbers) 80C7  
(*)  
80CE,  
80CF  
Duplicated  
number  
A40113 ON A409 (Duplicate Rack  
80E9  
Set the Rack No. and Unit No.  
again. Then turn the power OFF  
and ON again. Perform the error  
clear operation after corrective  
action has been taken.  
Number)  
A410 (CPU Bus Unit Du-  
plicate Number)  
CPU bus error  
I/O points over  
A40112 ON A405 (CPU Bus Unit Er- 8100-  
Check the cables between the  
CPU Rack and Expansion CPU  
Rack. Perform the error clear op-  
eration after corrective actions  
have been taken.  
ror Unit Number)  
8115  
(**)  
A40411 ON A407 (Total I/O Words  
on CPU and Expansion  
Racks)  
80E1  
Read the I/O table to check the  
number of words allocated. Cor-  
rect the table if necessary by  
creating a new one.  
A408 (Total SYSMAC  
BUS/2 I/O Words)  
A478 (Total SYSMAC  
BUS I/O Words)  
I/O setting error  
Program error  
OFF  
OFF  
A40110 ON None  
80E0  
80F0  
Verify the I/O table. Correct the  
table if necessary.  
A40109 ON None  
Correct the program. Perform the  
error clear operation after correc-  
tive actions have been taken.  
Cycle time over  
Fatal SFC error  
OFF  
A40108 ON A462/463 (Maximum  
Cycle Time)  
809F  
80F3  
Check the program or set time for  
monitoring the cycle.  
A464/465 (Present  
Cycle Time)  
OFF  
OFF  
A40107 ON A414 (SFC Fatal Error  
Code)  
Correct the program. Perform the  
error clear operation after correc-  
tive actions have been taken.  
System failure  
(FALS)  
A40106 ON None  
C101 to Check/correct the program.  
C2FF  
(***)  
Note *0 through 7 indicate rack numbers; E indicates series 0; F indicates series 1.  
**00 through 15 indicate unit numbers.  
***101 through 2FF indicate FALS numbers.  
78  
 复制成功!