Data Sheet  
GE  
CAR1212DC series DC-DC converter  
Input: -36VD C to -75VDC; Output: 12VDC @ 1200W; 3.3VDC or 5 VDC @ 1A  
The signal will be triggered for any state change, including the  
following conditions;  
Digital Feature Descriptions  
PMBus™ compliance: The power supply is fully compliant to the  
Power Management Bus (PMBus™) rev1.2 requirements.  
VIN and under or over voltage  
IOUT over current  
Over Temperature warning or fault  
Fan Failure  
Communication error  
PEC error  
Invalid command  
Manufacturer specific commands located between addresses 0xD0  
to 0xEF provide instructions that either do not exist in the general  
PMBus specification or make the communication interface simpler  
and more efficient.  
Master/Slave: The ‘host controller’ is always the MASTER. Power  
supplies are always SLAVES. SLAVES cannot initiate  
Internal faults  
communications or toggle the Clock. SLAVES also must respond  
expeditiously at the command of the MASTER as required by the  
clock pulses generated by the MASTER.  
The power supply will clear the SMBusAlert# signal (release the  
signal to its HI state) upon the following events:  
Receiving a CLEAR_FAULTS command  
The main output recycled (turned OFF and then ON) via the  
ENABLE signal pin  
Clock stretching: The ‘slave’ µController inside the power supply  
may initiate clock stretching if it is busy and it desires to delay the  
initiation of any further communications. During the clock stretch  
the ‘slave’ may keep the clock LO until it is ready to receive further  
instructions from the host controller. The maximum clock stretch  
interval is 25ms.  
The main output recycled (turned OFF and then ON) by the  
OPERATION command  
Execution of a READ of the STATUS_WORD register  
The host controller needs to recognize this clock stretching, and  
refrain from issuing the next clock signal, until the clock line is  
released, or it needs to delay the next clock pulse beyond the clock  
stretch interval of the power supply.  
Global broadcast: This is a powerful command because it can  
instruct all power supplies to respond simultaneously in one  
command. But it does have a serious disadvantage. Only a single  
power supply needs to pull down the ninth acknowledge bit. To be  
certain that each power supply responded to the global instruction,  
a READ instruction should be executed to each power supply to  
verify that the command properly executed. The GLOBAL  
BROADCAST command should only be executed for write  
instructions to slave devices.  
Note that clock stretching can only be performed after completion  
of transmission of the 9th ACK bit, the exception being the START  
command.  
Read back delay: The power supply issues the SMBAlert #  
notification as soon as the first state change occurred. During an  
event a number of different states can be transitioned to before the  
final event occurs. If a read back is implemented rapidly by the host  
a successive SMBAlert# could be triggered by the transitioning state  
of the power supply. In order to avoid the triggering of successive  
SMBAlert# s and thus reading a transitioning state, it is prudent to  
wait more than 2 seconds after the receipt of an SMBAlert# before  
executing a read back. This delay will ensure that only the final state  
of the power supply is captured.  
Clock  
Stretch  
Figure 13. Example waveforms showing clock stretching.  
Successive read backs: Successive read backs to the power supply  
should not be attempted at intervals faster than every one second.  
This time interval is sufficient for the internal processors to update  
their data base so that successive reads provide fresh data.  
I²C Bus Lock-Up detection: The device will abort any transaction  
and drop off the bus if it detects the bus being held low for more  
than 35ms.  
Communications speed: Both 100kHz and 400kHz clock rates are  
supported. The power supplies default to the 100kHz clock rate. The  
minimum clock speed specified by SMBus is 10 kHz.  
PMBusTM Commands  
Packet Error Checking (PEC): Although the power supply will  
respond to commands with or without the trailing PEC, it is highly  
recommended that PEC be used in all communications. The  
integrity of communications is compromised if packet error  
correction is not employed. There are many functional features,  
including turning OFF the main output, that should require  
validation to ensure that the correct command is executed.  
Standard instruction: Up to two bytes of data may follow an  
instruction depending on the required data content. Analog data is  
always transmitted as LSB followed by MSB. PEC is optional and  
includes the address and data fields.  
1
S
8
1
A
8
1
A
Slave address  
Wr  
Command Code  
PEC is a CRC-8 error-checking byte, based on the polynomial C(x) =  
x8 + x2 + x + 1, in compliance with PMBus™ requirements. The  
calculation is based in all message bytes, including the originating  
write address and command bytes preceding read instructions. The  
PEC is appended to the message by the device that supplied the last  
byte.  
8
1
A
8
1
A
8
PEC  
1
A
1
P
Low data byte  
High data byte  
Master to Slave  
Slave to Master  
SMBUS annotations; S – Start , Wr – Write, Sr – re-Start, Rd –  
Read, A – Acknowledge, NA – not-acknowledged, P – Stop  
SMBAlert#: The µC driven SMBAlert# signal informs the  
‘master/host’ controller that either a STATE or ALARM change has  
occurred. Normally this signal is HI. The signal will change to its LO  
level if the power supply has changed states and the signal will be  
latched LO until the power supply either receives a ‘clear’ instruction  
as outlined below or executes a READ STATUS_WORD. If the alarm  
state is still present after the STATUS registers were reset, then the  
signal will revert back into its LO state again and will latch until a  
subsequent reset signal is received from the host controller.  
October 21, 2013  
©2013 General Electric Company. All rights reserved.  
Page 10  