Data Sheet  
GE  
CAR1212DC series DC-DC converter  
Input: -36VD C to -75VDC; Output: 12VDC @ 1200W; 3.3VDC or 5 VDC @ 1A  
Environmental Specifications  
Parameter  
Ambient Temperature  
Min  
-106  
-40  
Typ  
Max  
70  
Units  
°C  
Notes  
Air inlet from sea level to 5,000 feet.  
Storage Temperature  
85  
°C  
Operating Altitude  
2250/7382  
8200/30k  
2.5  
m / ft  
m / ft  
%/°C  
Non-operating Altitude  
Power Derating with Temperature  
51°C to 70°C7  
Operating Temperature Derating with  
Altitude  
2.0  
°C/305 m  
°C/1000 ft  
Above 2250/7382 m/ft; 3962/13000 m/ft  
max  
Acoustic noise  
55  
dbA  
25°C, half load  
Humidity  
Operating  
Storage  
30  
10  
95  
95  
%
%
Relative humidity, non-condensing  
NEBS GR-63-CORE, Level 3, 20 -2000Hz, min  
30 minutes  
Shock and Vibration acceleration  
Earthquake Rating  
6
Grms  
Zone  
NEBS GR-63-CORE, all floors, Seismic Zone 4  
Designed and tested to meet NEBS  
specifications.  
4
EMC Compliance  
EMC  
Parameter  
Criteria  
Standard  
Level  
Test  
Conducted emissions  
EN55022, FCC Docket 20780 part 15, subpart J  
Telcordia GR1089-CORE, Class A  
A
0.15 – 30MHz  
DC input  
Radiated emissions  
Voltage dips  
EN55022  
A
B
B
B
A
A
30 – 10000MHz  
-30%, 10ms  
EN61000-4-11  
-60%, 100ms  
-100%, 5sec  
DC input  
immunity  
Voltage surge  
Fast transients  
EN61000-4-5  
2kV, 1.2/50µs, common mode  
1kV, 1.2/50µs, differential  
mode  
EN61000-4-4  
EN61000-4-6  
B
A
5/50ns, 1kV (common mode)  
Conducted RF fields  
Radiated RF fields  
130dBµV, 0.15-80MHz, 80%  
AM  
Enclosure  
immunity  
EN61000-4-3, level 3  
ENV50140  
A
A
B
10V/m, 80-1000MHz, 80% AM  
ESD  
EN61000-4-2, level 3  
6kV contact, 8kV air  
6
Designed to start at an ambient down to -40°C; meet spec after 30 min warm up period, may not meet operational limits below -10°C.  
7
The maximum operational ambient is reduced in Europe in order to meet certain power cord maximum ratings of 70°C. The maximum  
operational ambient where 70°C rated power cords are utilized is reduced to 60°C until testing demonstrates that a higher level is acceptable.  
October 21, 2013  
©2013 General Electric Company. All rights reserved.  