Data Sheet  
GE  
CAR1212DC series DC-DC converter  
Input: -36VD C to -75VDC; Output: 12VDC @ 1200W; 3.3VDC or 5 VDC @ 1A  
the Vprog pin is used for setting initial conditions, if different that  
Mfr-revision (9B): Total 4 bytes  
the factory setting. Software programming then takes over once I2C  
communications are established.  
Each byte is partitioned into high and low nibbles.  
Vout_OV[OT]_fault_limit (40[4F]): Provides the capability to change  
the OV[OT] shutdown limit. No sanity check exists to ensure that the  
changed value is within the expected range. However, if the value  
exceeds the maximum limit, the program will default to the  
maximum value.  
Example: FF is read as 16.16  
11 is read as 1.1  
Series  
Hardware Rev  
Primary µC  
Secondary µC  
Vout_OV[OT]_warn_limit (42[51]): OV[OT]_warning is extremely  
useful because it gives the system controller a heads up that the  
output voltage/temperature is drifting out of regulation and the  
power supply is close to shutting down. Preemptive action may be  
taken before the power supply would shut down and potentially  
disable the system.  
Mfr_serial (9E): Product serial number includes the manufacturing  
date, manufacturing location in up to 15 characters. For example:  
13KZ51018193xxx, is decoded as;  
13 – year of manufacture, 2013  
OC and OT_fault_ response (47, 50): The default response for OC is  
latched on fault. The response for OT is auto_restart once internal  
temperatures cool down.  
KZ – manufacturing location, in this case Matamoros  
51 – week of manufacture  
018193xxx – serial #, mfr choice  
Restart after a latch off: Either of four restart possibilities are  
available. The hardware pin Remote ON/OFF may be turned OFF  
and then ON. The unit may be commanded to restart via i2c  
through the Operation command by first turning OFF then turning  
ON . The third way to restart is to remove and reinsert the unit. The  
fourth way is to turn OFF and then turn ON ac power to the unit.  
The fifth way is by changing firmware from latch off to restart.  
Each of these commands must keep the power supply in the OFF  
state for at least 2 seconds, with the exception of changing to  
restart.  
note: if the additional xxx space is not utilized then F’s are filled  
in, (i.e. 018193FFF), ensuring that the actual serial number is clearly  
identified.  
Invalid commands or data: The power supply notifies the MASTER if  
a non-supported command has been sent or invalid data has been  
received. Notification is implemented by setting the appropriate  
STATUS and ALARM registers and setting the SMBAlert# flag. An  
invalid command always returns a value of 0 x 00.  
A power system that is comprised of a number of power supplies  
could have difficulty restarting after a shutdown event because of  
the non-synchronized behavior of the individual power supplies.  
Implementing the latch-off mechanism permits a synchronized  
restart that guarantees the simultaneous restart of the entire  
system.  
Control and Read accuracy:  
The estimates below are believed to be reasonable under most  
operating conditions. However, these are typical numbers and not  
hard bound values that cannot be exceeded. In most nominal  
operating conditions the returned values are significantly better  
than these estimates.  
A synchronous restart can be implemented by;  
FUNCTION  
ACCURACY  
± 3%  
± 3%  
± 4% of FL  
± 5°C8  
± 3%  
1. Issuing a GLOBAL OFF and then ON command to all power  
supplies,  
2. Toggling Off and then ON the Remote ON/OFF signal  
3. Removing and reapplying input commercial power to the entire  
system.  
Vout_command  
Vout_OV_fault_limit  
Iout_OC_warn_limit  
OT_warn_limit  
Read_Vout  
The power supplies should be turned OFF for at least 20 – 30  
seconds in order to discharge all internal bias supplies and reset the  
soft start circuitry of the individual power supplies.  
± 4% of FL  
± 5°C9  
Read_Iout  
Read_temperature  
Auto_restart: Auto-restart is the default configuration for  
recovering from over-current and over-temperature shutdowns.  
EEPROM  
An overvoltage shutdown is followed by three attempted restarts,  
each restart delayed 1 second, within a 1 minute window. If within  
the 1 minute window three attempted restarts failed, the unit will  
latch OFF. If less than 3 shutdowns occur within the 1 minute  
window then the count for latch OFF resets and the 1 minute  
window starts all over again.  
The microcontroller has 96 bytes of EEPROM memory available for  
the system host.  
Another separate EEPROM IC will provide another 128 bytes of  
memory with write protect feature.  
Status_word (79): returns two bytes of information. The upper byte  
bit functionality is tabulated in the Status_word section. The lower  
byte bit functionality is identical to Status_byte.  
LEDs  
Three LEDs are located on the front faceplate. When the LEDs are  
ON GREEN then input and output are normal.  
Fan_speed (3B): Fan speed can be controlled either by changing the  
RPM or duty cycle via register 3B. Selection of RPM or duty cycle  
control is accomplished by bit 6 of the FAN_CONFIG_1_2 (3A)  
command. The default mode is xxxx The speed of the fan cannot be  
reduced below what the power supply requires for its operation.  
The number represented in register D6 is an unsigned number, it is  
not in linear format.  
When the FAULT_LED is RED, then a fault condition exists and the  
power supply may not provide output power. The table below  
further defines these states:  
Mfr_ID (99): Manufacturer in ASCII – 5 characters maximum,  
General Electric – Critical Power represented as,  
GE-CP  
8
Accuracy is estimated near the shutdown point around 100°C. At lower  
temperatures the accuracy is much reduced.  
9
Accuracy is estimated near the shutdown point around 100°C. At lower  
temperatures the accuracy is much reduced.  
October 21, 2013  
©2013 General Electric Company. All rights reserved.  
Page 13  
 
 