Hazardous Location
CONTROL DRAWING FOR SINGLE CHANNEL BARRIERS
Hazardous Location
Non-hazardous Location
Speed Sensor
Intrinsic Safety Barrier
GENERAL NOTES
HAZARDOUS LOCATIONS
Catalog listing 3042H20:
Class I, Groups A, B, C, D
Class II, Groups E, F, G
Class III
1. For jurisdictions requiring certification to the applicable
Canadian standards, the barrier must be CSA Certified
and the system must be installed in accordance with the
Canadian Electrical Code Part 1.
2. For jurisdictions requiring certification to the applicable
Occupational Safety and Health Administration (OSHA)
standards, the barrier must be CSA NRTL or equivalent
and the system must be installed in accordance with the
National Electrical Code (NEC), article 504 or
ANSI/NFPA 70.
Catalog listing 3042A:
Class I, Groups A, B, C, D
ENTITY PARAMETERS
Vmax = 24 V, Imax = 35 mA, Li = 26 mH, Ci = 0 μF
Any barrier (see General Notes) with entity parameters
connected in accordance with barrier manufacturers
instructions of:
SENSOR GROUNDING
Catalog listing 3042A: Sensor housing must be connected to
intrinsically safe system ground during installation.
Vmax > Voc
Imax > Isc
Ca > Ci + cable capacitance
La > Li + cable inductance
Catalog listing 3042H20: Green wire must be connected to
intrinsically safe system ground.
SYSTEM PARAMETERS
Any barrier (see General Notes) having one of the following
specified parameters:
Exia = Intrinsically Safe, Sécurité Intrinsèque
Vmax
30
25
Rmin
707
580
Vmax
20
15
Rmin
421
278
Vmax
10
Rmin
136
5
1
6
www.honeywell.com/sensing