 浏览型号AMIS-30623-AGA的Datasheet PDF文件第21页浏览型号AMIS-30623-AGA的Datasheet PDF文件第22页浏览型号AMIS-30623-AGA的Datasheet PDF文件第23页浏览型号AMIS-30623-AGA的Datasheet PDF文件第24页浏览型号AMIS-30623-AGA的Datasheet PDF文件第26页浏览型号AMIS-30623-AGA的Datasheet PDF文件第27页浏览型号AMIS-30623-AGA的Datasheet PDF文件第28页浏览型号AMIS-30623-AGA的Datasheet PDF文件第29页  
AMIS-30623 LIN Microstepping Motordriver  
Data Sheet  
15.2.7. Autarkic functionality in under-voltage condition  
Battery voltage management  
The AMIS-30623 monitors the battery voltage by means of one threshold and one shutdown level, as illustrated in the state diagram  
below. The only condition to reset flags <UV2> and <StepLoss> is to recover a battery voltage higher than UV1 and to receive a  
GetStatusor a GetFullStatuscommand.  
Normal voltage  
UV2  
> = ‘0’  
StepLoss  
- <  
- <  
Vbb < UV2  
&
> = ‘0’  
motion ongoin g  
Vbb < UV2  
(no motion)  
Vbb > UV1  
LIN frame:  
GetStatus  
&
or  
GetFullStatus  
Stop mode 1  
UV2  
Stop mode 2  
- <  
- <  
> = ‘ ’  
StepLoss  
1
- <  
- <  
UV2  
> = ‘ ’  
1
StepLoss  
> = 1’  
> = ‘0’  
HardStop  
-
- Motor shutdown  
(motion disabled)  
- Motor shutdown  
(motion disabled)  
Figure 17: State Diagram Battery Voltage Management  
Autarkic function  
In Stop mode 1 the motor is put in shutdown state. The <UV2> flag is set. In case Vbb > UV1 AMIS-30623 accepts updates of the  
target position by means of the reception of SetPosition, SetPositionShort, SetPosParam and GotoSecurePosition  
commands, even if the <UV2> flag is NOT prior cleared.  
In Stop mode 2 the motor is stopped immediately and put in shutdown state. The <UV2>and <Steploss>flags are set. In case Vbb  
> UV1 AMIS-30623 autonomously resumes the motion to the original target position using the stored motor parameters (minimum and  
maximum velocity, acceleration, step-mode, run- and hold current) in case no RAM reset occurred.  
The flags are only cleared after receiving a GetStatusor GetFullStatuscommand.  
Updates of the target position by means of the reception of SetPosition, SetPositionShort, SetPosParam and  
GotoSecurePositioncommands is accepted, even if the <UV2> and <Steploss> flags are NOT prior cleared.  
Important notes:  
1. In the case of Stop mode 2 care needs to be taken because the accumulated steploss can cause a significant deviation  
between physical and stored actual position.  
2. The SetDualPositioncommand will only be executed after clearing the <UV2> and <Steploss> flags.  
3. RAM reset occurs when Vdd < VddReset (digital Power On Reset level)  
4. The Autarkic function remains active as long as Vdd > VddReset  
Logical implementation Autarkic function  
The logic uses the <UV2>, <CPFail> and <Steploss> signal NOT the state.  
The state is set one clock after the signal and would therefore slow down the reaction time. Also the state can only be cleared after a  
GetStatusor GetFullStatuscommand which prevents the autonomous function.  
Only <UV2> and <CPFail> are applicable for finishing the motion to the original target position:  
<UV2> needs to be cleared to leave the Shutdown State  
<CPFail> needs to be cleared to avoid a new HardStopafter entering the GotoPosstate  
AMI Semiconductor – June 2006, Rev 3.0  
25  
www.amis.com  
 