欢迎访问ic37.com |
会员登录 免费注册
发布采购

1ZU2.5 参数 Datasheet PDF下载

1ZU2.5图片预览
型号: 1ZU2.5
PDF下载: 下载PDF文件 查看货源
内容描述: [Thermal Magnetic Circuit Breaker,]
分类和应用: 电路保护
文件页数/大小: 32 页 / 1762 K
品牌: ALTECH [ ALTECH CORPORATION ]
 浏览型号1ZU2.5的Datasheet PDF文件第23页浏览型号1ZU2.5的Datasheet PDF文件第24页浏览型号1ZU2.5的Datasheet PDF文件第25页浏览型号1ZU2.5的Datasheet PDF文件第26页浏览型号1ZU2.5的Datasheet PDF文件第28页浏览型号1ZU2.5的Datasheet PDF文件第29页浏览型号1ZU2.5的Datasheet PDF文件第30页浏览型号1ZU2.5的Datasheet PDF文件第31页  
V-EA AND MA  
CIRCUIT BREAKER  
ACCESSORIES  
Accessories can be factory or field  
mounted on V-EA miniature circuit  
breakers and MA motor protection  
switches for enhanced control and  
monitoring  
capabilities.  
Field  
mounting kits include all necessary  
parts and instructions. Accessories  
can be gang mounted on a single  
breaker (the Auxiliary Switch in the  
outside position). The mounting  
arrangement links the internal latch-  
pins for the tripping mechanisms,  
FA  
UA  
ensuring  
simultaneous  
trips.  
Shunt Trip  
Undervoltage Trip  
Handles are linked to simplify  
manual resetting.  
Trip/Coil  
Line Voltage  
50/60Hz  
Type/  
Voltage  
AC/DC  
Max. Coil  
Type  
Cat. No.  
Cat. No.  
Current  
Approvals  
U
L
FA12U  
12V  
24V  
1.3A  
0.6A  
0.2A  
0.25A  
0.5A  
0.8A  
UA120  
UA208  
UA240  
UA277  
UA254  
UA480  
120VAC  
208VAC  
240VAC  
277VAC  
254VAC  
480VAC  
15.956  
15.957  
15.951  
15.958  
15.959  
15.955  
U
L
FA24U  
U
L
FA48U  
48-72V  
110V  
FA110Ua  
FA110Ua  
FA110Ua  
U
L
U
L
220V  
U
L
380VAC  
Std.Pk.: 1  
Std.Pk.: 1  
Unit Weight: 70 grams (0.16 lb.)  
Width: 17.5mm (.689in.)  
Unit Weight: 120 grams (0.27 lb.)  
Width: 17.5mm (.689in.)  
Coil actuated, the FA Shunt Trip allows  
electrical remote tripping of a breaker. It  
is trip-free and the housing and terminal  
specifications are the same as for V-EA  
miniature circuit breakers.The Shunt Trip  
contains its own contacts which break  
the tripping power circuit when tripped. It  
is available with trip-coils in most  
standard control voltages. The device is  
UL and CSA listed for general use.  
Re-power your system under controlled  
conditions following a power loss or  
serious undervoltage. Altech/Sursum UA  
Undervoltage Trips are coupled to the  
tripping latch pins of the V-EA or MA to  
which they are attached, reliably produc-  
ing trips at the drop-out voltage and  
preventing resetting when less than 85%  
line voltage is present. The Undervoltage  
Trip is provided with at least 6-inch  
pigtails of stranded fixture wire for hook-  
up to the V-EA or MA line terminals.  
• Reset-Hold Voltage = 0.85 x Ve  
• Drop-Out Voltage = 0.35 to 0.7 x Ve  
a
One device with wide voltage range.  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
30  
 复制成功!