FI EARTH LEAKAGE  
CIRCUIT BREAKERS  
FI compact Earth Leakage Circuit  
Breakers detect and interrupt earth  
(ground) faults. They are VDE  
approved for the European system  
of protecting people, animals,  
equipment and property from  
dangerous line-to-ground and shock  
hazard currents.  
US applications include ground-fault  
protection of equipment (GFPE)  
using the 10mA and 30mA fault  
current ratings, especially when high  
distributed capacitance or other  
leakages cause excessive nuisance  
trips at lower fault currents.  
Applications for the 300mA rating are  
equipment protection and fire  
prevention, limiting the energy of a  
fault to less than the minimum  
ignition energy for many materials.  
a
FI 2  
FI 4  
Maximum  
Rated  
Line  
Fault  
Trip  
Fault  
Trip  
Current  
Current  
Current  
Type  
Cat. No.  
Type  
Cat. No.  
16A  
10mA  
FI 21.01 15.921  
25A  
25A  
30mA  
FI 22.03 15.922  
FI 22.30 15.924  
30mA  
300mA  
FI 42.03  
FI 42.30  
15.926  
15.929  
300mA  
40A  
40A  
30mA  
FI 23.03 15.923  
FI 23.30 15.925  
30mA  
300mA  
FI 43.03  
FI 43.30  
15.927  
15.930  
300mA  
Type Designation  
63A  
63A  
30mA  
300mA  
FI 44.03  
FI 44.30  
15.928  
15.931  
__  
__  
__  
(c)  
FI  
(a) (b)  
(a) = 2-2 pole; 4-4 pole  
(b) = 1-16A; 2-25A; 3-40A; 4-63A  
(c) = 01 - 10mA  
Earth Leakage Circuit Breaker  
Earth Leakage Circuit Breaker  
with Auxiliary Contactsb  
with Auxiliary Contactsb  
25A  
40A  
63A  
30mA  
30mA  
FI 22.03Y 15.932  
FI 23.03Y 15.934  
30mA  
30mA  
30mA  
FI 42.03Y  
FI 43.03Y  
FI 44.03Y  
15.933  
15.935  
15.936  
= 03 - 30mA  
= 30 - 300mA  
Voltage Rating (maximum)  
Short Circuit Capacity  
240VAC, 50/60Hz  
(VDE: 125/220VAC, 50Hz)  
415VAC, 50/60Hz (400Hz available on request)  
(VDE: 220/380VAC, 50Hz)  
Up to rated current (RC) 40A = 1.5kA, RC 63A = 2kA. 10kA in combination with series fuse of  
European Operation Class gL/gG: RC 16A = 63A fuse, RC 20/40A = 80A fuse, RC 63A = 100A fuse.  
Fault Trip Current Calibration  
FI trips are calibrated at less than fault trip current for ensured safety (Typical trip range between  
66.6-83.3% fault trip current, e.g., typical trip at 20-25mA for fault RC of 30mA)  
Typical Life  
Fully functional after 4,000 operations to DIN/VDE 0664 (CEE27) and 16000 additional fault current trips.  
Standard Pack and Weight  
1/290g (0.64 lb.);  
1/450g (1.0 lb.)  
1/390g (0.86 lb.) with auxiliary contact  
1/550g (1.21 lb.) with auxiliary contact  
Terminal Size Acceptability  
Equivalent Circuit  
16-6 AWG  
14-3 AWG  
1
N
1 3 5 N  
2
N
Test  
2 4 6 N Test  
a
For 2-Phase applications, terminal 5 and 6 (next  
to Neutral terminals) must be connected to one  
phase for the test circuit to be operable.  
Note: If the power system has a marked conductor, it must connect through the FI and not be grounded at any  
point downstream.  
b
Provided with mounted Auxiliary Switch, one N.O.,  
one N.C. isolated feedthrough contact (Form X  
double make and Y double break), which adds  
9mm (.35 in.) to the width dimension.  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  