欢迎访问ic37.com |
会员登录 免费注册
发布采购

1ZU2.5 参数 Datasheet PDF下载

1ZU2.5图片预览
型号: 1ZU2.5
PDF下载: 下载PDF文件 查看货源
内容描述: [Thermal Magnetic Circuit Breaker,]
分类和应用: 电路保护
文件页数/大小: 32 页 / 1762 K
品牌: ALTECH [ ALTECH CORPORATION ]
 浏览型号1ZU2.5的Datasheet PDF文件第22页浏览型号1ZU2.5的Datasheet PDF文件第23页浏览型号1ZU2.5的Datasheet PDF文件第24页浏览型号1ZU2.5的Datasheet PDF文件第25页浏览型号1ZU2.5的Datasheet PDF文件第27页浏览型号1ZU2.5的Datasheet PDF文件第28页浏览型号1ZU2.5的Datasheet PDF文件第29页浏览型号1ZU2.5的Datasheet PDF文件第30页  
64mm (2.52 in.)  
58mm (2.28 in.)  
8mm  
13.5mm  
13.5mm  
13.5mm  
5.8mm  
(0.23 in.)  
10.9mm  
(0.43 in.)  
22.9mm  
(0.90 in.)  
(0.31 in.) (0.53 in.) (0.53 in.) (0.53 in.)  
1
N
1
3
5
N
46°  
2
N
2
4
6
N
6.5mm  
(0.26 in.)  
3.2mm  
15.7mm  
(0.13 in.) (0.62 in.)  
31mm (1.22 in.)  
9mm  
18mm  
9mm  
18mm  
18mm  
(0.71 in.)  
18mm  
(0.71 in.)  
(0.35 in.) (0.71 in.)  
(0.35 in.) (0.71 in.)  
44mm (1.73 in.)  
72mm (2.83 in.)  
36mm (1.42 in.)  
68mm (2.68 in.)  
FI 2  
FI 4  
FI 2 and FI 4  
Temperature Range  
Environmental Information marked with “Snowflake” approval for -25°C to 40°C (-13°F to 104°F) ambient  
temperature. (Temperature effect on RC: for every 10°C temperature rise above 40°C decrease RC by 7%.)  
Fluctuating Climate Conditions  
Electrical Shock Protection  
To maximum 45°C, 95% relative humidity.  
Uninsulated electrically live parts within 30mm of the operating handle are “finger safe” (terminal screw  
heads) and uninsulated live parts within 100mm of the operating handle are “back-of-hand safe” (terminals).  
15g with impact force half-cycle sinusoidal and 11ms duration, 18 impacts total with 6 on each principal axis  
(3 impacts each face). FI is DIN Rail mounted during the test, and electrically loaded with 25% of Fault RC.  
Successful testing required no trip during the test, no damage and no loosened parts.  
Impact/Shock Protection  
5g, at frequency of 55Hz to 2,000Hz, applied for 35 ± 5 minutes along each of the three principal axes, plus  
5 minutes of application at every established critical resonant frequency. FI is DIN Rail mounted during the  
test, and loaded with 25% Fault RC. To pass, the FI did not trip at 25% Fault RC, but did trip between each  
of the principal axis tests when the fault current was raised to 125% Fault RC, and there was no damage  
and no loosened parts. Suitable for machinery and mobile vehicle applications.  
Vibration/Seismic Resistance  
Ingress Protection (IP) Class 40; internal working components and live parts (excluding terminals) are  
protected against ingress of solid objects greater than 1mm diameter (class 4-), but have no protection from  
ingress of water (class-0).  
Housing Class  
The FI is tested and approval stamped for tripping sensitivity to non-sinusoidal fault currents, which become  
zero or almost zero within one cycle of the line frequency. Waveforms and allowed trip-current ranges are as  
follows:  
Non-Sinusoidal Fault  
1.  
AC Sinusoidal Fault - 0.5-1.0 times Fault RC  
2a.  
2b.  
Pulsating DC Fault;  
Positive and Negative Half-Waves - 0.35-1.4 times Fault RC  
Phased Half-Wave, 90° - 0.25-1.4 times Fault RC  
Phased Half-Wave, 135° - 0.11-1.4 times Fault RC  
3.  
Pulsating DC on 6mA  
DC (continuous) Base - Max. 1.4 times Fault RC + 6mA  
At VDE rated voltage, suitable for Class C environments with relatively high dust and moisture levels and  
little HVAC control, e.g., industrial, commercial, agricultural; on machine tools, hoists, warehouse equipment,  
etc.; in boiler rooms, unheated storage, covered shipping/receiving, open workshops, etc.  
Insulation Category  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  