G70D-R6††1-B7A
G70D-R6††1-B7A
Item
Classification
G70D-R6R 1-B7A
G70D-R6M 1-B7A
P
P
Relay outputs
Power MOSFET relay outputs
Contact form
16 points (SPST-NO x 16)
Contact mechanism
Contact material
Single
---
AgCdO
100 mΩ max.
---
---
Contact resistance (See Note 2)
Insulation method
Operate time
---
Photodiode array
6 ms max.
10 ms max.
10 ms max.
---
Release time
Output ON-resistance
Leakage current for closed relay
Max. switching frequency
2.4 Ω max.
---
10 µA max. (at 125 VDC)
Mechanical: 18,000 operations/hr
Rated load: 1,800 operations/hr
---
Insulation resistance
Dielectric strength
Noise immunity
100 MΩ min. (at 500 VDC)
1,000 VAC for 1 min between each terminal and external parts
Power supply normal:
Power supply common:
600 V for 10 min with a pulse width of 100 ns to 1 µs
1.5 kV for 10 min with a pulse width of 100 ns to 1 µs
Coiling around transmission path: 1.5 kV for 10 min with a pulse width of 100 ns to 1 µs
Coiling around Unit: 600 V for 10 min with a pulse width of 100 ns to 1 µs
Vibration resistance
Shock resistance
Destruction: 10 to 55 Hz, 1.0-mm double amplitude for 2 hrs each in X, Y, and Z directions
Malfunction: 10 to 55 Hz, 0.75-mm double amplitude for 2 hrs each in X, Y, and Z directions
2
Destruction: 300 m/s (approx. 30G)
2
Malfunction: 100 m/s (approx. 10G)
+10%
Operating voltage range
Current Consumption
Cable length
24 VDC
/
--15%
Approx. 300 mA at 24 VDC
Between block and controller:
500 m (1640 ft) max. (reference value for AWG28)
Between block and external device:Dependent on load
Operation indicator: orange; power supply: green (red for errors)
Diode (400 V, 300 mA)
LED color
Coil surge absorber
Life expectancy
Electrical: 100,000 operations min. (3 A at 250 VAC/30 VDC, resistive load)
300,000 operations min. (2 A at 250 VAC/30 VDC, resistive load)
(at 1,800 operations/hr)
Mechanical: 20,000,000 operations min. (at 18,000 operations/hr)
Ambient temperature
Operating: 0°C to 55°C (32°F to 131°F)
Storage: --20°C to 65°C (--4°F to 149°F)
Ambient humidity
Mounting strength
Operating: 35% to 85%
No damage when 5 kgf (49 N) pull load was applied for 1 s in all directions
(except for 1 kgf (9.8 N) in direction of DIN rail)
Terminal strength
Weight
Tightening torque: 8 to 10 kgf : cm (0.78 to 0.98 N : m)
Pull strength:
5 kgf (49 N) for 1 min
Approx. 230 g
Note: 1. The above values are initial values.
2. Measurement condition: 1 A at 5 VDC
3. Current consumption is when all points are ON and includes G6D relay coil current. External load current and error output cur-
rent are not included.