AC-DC Power Supplies
ALM85 Series
General
Characteristic
Minimum
Typical
Maximum
Units
%
Notes & Conditions
See curves.
Efficiency
88
4000
1500
500
VAC
VAC
VAC
kHz
2 x MOPP
Isolation: Input to Output
Input to Ground
1 x MOPP (Class I versions only)
Class I versions only
PWM
Output to Ground
Switching Frequency
Power Density
65 KHz
4.55
3
W/in
Mean Time Between Failure
Weight
>300
kHrs
lb (g)
MIL-HDBK-217F at 25 °C GB
0.78 (355)
Efficiency Curves
ALM85US12
100.00%
90.00%
80.00%
70.00%
60.00%
115V
230V
10%
20%
30%
40%
50%
60%
70%
80%
90% 100%
Load
ALM85US24
100.00%
90.00%
80.00%
70.00%
60.00%
115V
230V
10%
20%
30%
40%
50%
60%
70%
80%
90% 100%
Load
EMC: Emissions
Phenomenon
Standard
Test Level
Notes & Conditions
Conducted & Radiated
Emissions
Harmonic Current
Voltage Flicker
EN55022
EN61000-3-2
EN61000-3-3
Level B
Class A
www.xppower.com